Franklin Fueling Systems T5 Series Fuel Management System Programming Guide User Manual
Page 27

23
4-20 mA and 4-20 mA EXP Input Modules
The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface.
The 4-20 mA EXP module is programmed in the same manner. The 420 EXP module is located on the hazardous side of
the console, must have the wires enclosed in explosion-proof conduit, and has a red front. If a DTU is being used there
will be an option for a “virtual module” labeled Remote Module. The Remote Module gathers information from the vapor
pressure sensor when a DTU is used. (see DTU Programming for further details on page 31 in this manual.)
Group Name
Parameter
Name
Parameter
Default
Description
Parameter Input
4-20mA Input Modules
Module #
Channels
(0)
Number of channels in use per module.
0-8
Channel #
Name
(4-20mA Input 1)
Given name of the channel.
abc#
Service Type
(Analog)
Determines the input signal.
Analog
Secondary Containment Monitoring
Line Leak Detection
Vapor Recovery Monitoring
FMS Level Probe
Low Range
-8.00
Low range of mA input
- #
High Range
8.00
High range of mA input
+ #
#3 Remote
Module 2 (DTU) Channels
(0)
Number of channels in use
0-5
Name
4-20 mA input 6
Given name of the channel
abc#
Service Type
(Vapor Recovery)
Determines the output signal
Vapor Recovery Monitoring