32

E-Mail

Group Name

Parameter Name

Parameter

Default

Description

Parameter

Input

E-Mail

“From” Address

your_from@address.

com

Address of sender (console).

abc

SMTP Host

your_smtp_host_

address

IP address of SMTP Host.

#

SMTP Port

25

Port address of SMTP.

#

Enable Authentication

No

Data authentication (if required).

Yes / No

Maximum Queue Size

20

Maximum size of queue in Megabytes.

Retry Timeout

3600

Time, in seconds, that the console will wait before attempting

to resend the message.

Watchdog Timeout

30

Time, in seconds, that the console self-monitoring program

waits when it expects and error due to software or power

quality problems.

Enable Debugging

(No)

Select Yes if you would like more status information to be

stored in the Messages file.

Yes / No

System Sentinel Anyware

This section will be filled out automatically upon the initial polling by System Sentinel Anyware.

Events

Group Name

Parameter Name

Parameter Default

Description

Options

Rules

: Rules are a logic-based programming that are driven off of “If” based Events and “Then” Based actions. Essentially: “If” this event occurs

“Then” the console will perform a specified action.

Rule – New Rule #

Name

(New Rule #)

Given name of rule.

abc#

Enabled

(No)

Yes to enable rule.

Yes/No

Events: Events can be both “If” logic and “Or” Logic. Therefore you can have several events trigger the same action. “If” Event 1 “Or” Event 2

occurs the console will perform a specified action.

Event

Type

(New Alarm Occurred)

Event type that triggers action.

New Alarm Occurred;

Alarm Status Changed;

Application Event;

Scheduled

Category

(Any)

System that event occurs in to trigger

action.

Any;

System;

FMS;

VRM;

SCM;

Other

Code

(Any)

Error/Trouble Event Code that triggers

action.

(see below)

Device

(Any)

Device that created the alarm

condition.

Various

State

(Any)

State of alarm to trigger action.

Various

Action: Actions are sequentially “Then” / ”And” driven. Therefore, “If” an Event occurs “Then” the console will perform Action 1 and then Action

2 and then Action 3.

Action

Type

(e-mail)

Action that will occur upon event

E-mail, Report, Relay, Tank

Testing, Line Testing, Sentinel

mode, Reconciliation, sound,

Notify SSA, Sample input,

STP Control, Generator

Address

your,[email protected]

Where it will send e-mail

Contact

Generated

What e-mail format is used

Generated, Text, HTML, Other

Template

Text

E-mail Template

HTML, Text, short text