Xylem CHATTER RTU and E-mail User Manual
Page 85

USERS MANUAL
CHATTER™ DATA LOGGER
85
Select between No and Yes.
If you select Yes, the Chatter™ Data Logger will make
an alarm call using the Alarm call list when an alarm
condition no longer exists.
A dditional inform ation:
Use alarm retention interval
Select between No and Yes.
If you select Yes, the Chatter™ Data Logger will make
an alarm call using the Alarm call list when an alarm
condition exists. It will not react to new alarms from
this analog input before the Alarm retention interval
runs out.
If you select
N o
, the Chatter™ Data Logger will make
an alarm call for every new alarm on this analog input.
You will get repeated alarms from this
input if an alarm is started on another input
before the alarm retention time runs out..
Any new alarm on an input calls all entries
in the Alarm call list and delivers alarm
status for all inputs to the recipients.
Additional information:
Setting the alarm retention interval
Setting the alarm call list
Scale 0V
The default value is 0, please read about Scaling and Calibration before you change this value.
A dditional inform ation:
Scaling and calibration
Changing output values
Scale 2,5V
The default value is 2,5, please read about Scaling and Calibration before you change this value.
A dditional inform ation:
Scaling and calibration
Changing output values
Calibration 0V
The default value is 0, please read about Scaling and Calibration before you change this value.
A dditional inform ation:
Scaling and calibration
Changing output values
Calibration 2,5V
The default value is 2,5, please read about Scaling and Calibration before you change this value.