Alarm

Use this window to set the way each of the four digital
input will operate.

The data shown are only accurate when
your PC is connected to the Chatter™
Data Logger with a USB-cable, otherwise it
will show the data from the last time, you
were connected to the Chatter™ Data
Logger

A dditional inform ation:

Setup pane
Advanced pane

Call on alarm ON

Select between No and Yes.

If you select Yes, the Chatter™ Data Logger will make an
alarm call when it encounters an alarm condition. It will
call all entries in the Alarm call list, starting with the first
entry.

Additional information:

Call lists
Setting the alarm call list

Call on alarm OFF

Select between No and Yes.

If you select Yes, the Chatter™ Data Logger will make an
alarm call when the alarm condition no longer exists. It
will call all entries in the Alarm call list, starting with the
first entry.

A dditional inform ation:

Call lists
Setting the alarm call list

Use alarm retention interval

Select between No and Yes.

If you select Yes, the Chatter™ Data Logger will make an
alarm call using the Alarm call list when an alarm
condition exists. It will not react to new alarms from this
digital input before the Alarm retention interval runs out.

If you select No, the Chatter™ Data Logger will make an
alarm call for every new alarm on this digital input.

You will get repeated alarms from this input if
an alarm is started on another input before the
alarm retention time runs out.. Any new alarm
on an input calls all entries in the Alarm call list
and delivers alarm status for all inputs to the
recipients.

A dditional inform ation:

Setting the alarm retention interval