General setup parameters, Location in register list – Xylem CHATTER RTU and E-mail User Manual
Page 188

USERS MANUAL
CHATTER™ DATA LOGGER
188
General setup parameters
Name
Reg
#
Modbus
R/W
Typ
e
FW
Description
Station ID
2
R/W 3/16 U16
Used for ID device in SCADA system (not used
internally in device) Default is 0, not in use
RTU Name/ID Tag
7
R/W 3/16 STR
20
RTU Name / Location Name Default = "Chatter1" ( 1
Depends on Device ID)
Last Battery measurement
18
R 3
U16
Last battery measurement after use of modem for
last call [mV]
0 = Unknown / not updated yet
< 3000mV = Replace battery
3500 - 3700mV = OK, but this value is depending
on how long the last connection was.
MJK Serial No
28
R 3
U32
MJK serial no. identifying Chatter™ Data Logger
when contacting MJK
GSM signal-strength
30
R 3
U16
0-31 (99 = Unknown or not ready yet)
Second
40
R/W 3/16 U16
ex 59 = 59sec (sec .. to year must be written in one
telegram)
Minute
41
R/W 3/16 U16
Hour
42
R/W 3/16 U16
Day
43
R/W 3/16 U16
Month
44
R/W 3/16 U16
Year
45
R/W 3/16 U16
Modem Online Time left
46
R/W 3/16 U16 85000
7
Modem time left for call at this time [sec] Restarted
daily.
If 0, the Chatter™ Data Logger is not allowed to
make any calls before next daily reset