GE Industrial Solutions CPS6000 User Manual
Page 83

CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
83
Serial Port
The appropriate IP address, subnet mask, hostname, and default gateway IP
address must be configured on the QS841A through serial port J3.
To login to the QS841A, follow these steps:
a. Start-up the PC terminal program (Windows Terminal,
ProComm, etc.) using the following communication
parameters:
Baud : 9600
Data : 8
Parity : none
Stop : 1
Handshaking: none
Flow Control: none
b. Connect the PC to the QS841A local port (RS-232) connector
J3
c. Wait for any diagnostic messages to pass.
d. Wait for the “ENTER PASSWORD:” command line prompt.
e. Type the Network Administrator password (default:
administrator).
f.
Wait for the “$” prompt.
8A Configuring
Static Network Parameters
After a valid password entry, a login header with the following format similar
to that below will be displayed:
Board Code
QS841A
Serial Number 05DJ09112345
Boot Block
version 1.0
Application Code
version 1.0
Default Web Pages
version 1.0
Custom Web Pages
not found
Ethernet Address
00-60-1D-00-5C-07
IP Address
not configured
Subnet Mask not configured
Default Gateway
not configured
Host Name
not configured
For assistance type help
$
Typing HELP at the “$” will show all available network administration
commands and command line formats.
*note: 1) commands are not case sensitive
2) for the commands that follow, ddd is a number from 0 – 255
• To set the IP Address, type: