GE Industrial Solutions CPS6000 User Manual
Page 169

CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
169
Alarm Thresholds/Relays
Related Commands
obj,attr
description sta
cha
ope
type
range
of
values
bda1,acc
Battery on discharge relay
x x
text “R1” ,“R2”, “R3”, “R4”, or “”
bda1,ast
Battery on discharge alarm state
x
number 0:not
active
1:active
bda1,sev
Battery on discharge severity
x x
text “MAJ”,“MIN” , or “RO"
bda1,thr
Battery on discharge threshold
x x
number 46-55:51V
bta1,acc
High battery temperature relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
bta1,ast
High batt temperature alarm state
x
number 0:not
active
1:active
bta1,sev
High battery temperature severity
x x
text “MAJ”,
“MIN” , or “RO"
bta1,thr High
battery
temperature
x x
number 30-85:55C
hfv1,acc High
voltage
relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
hfv1,ast
High voltage alarm state
x
number 0:not
active
1:active
hfv1,bth
High boost voltage threshold
x x
number 50-60:56V
hfv1,fth
High float voltage threshold
x x
number 50-60:56V
hfv1,sev High
voltage
severity
x x
text “MAJ”,
“MIN” , or “RO"
hva1,acc
Very high voltage relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
hva1,ast
Very high voltage alarm state
x
number 0:not
active
1:active
hva1,bth
Very high boost voltage threshold
x x
number 50-60:57V
hva1,fth
Very high float voltage threshold
x x
number 50-60:57V
hva1,sev
Very high voltage severity
x x
text “MAJ”, “MIN” , or “RO"
rtl1,acc
Reserve time low relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
rtl1,ast
Reserve time low alarm state
x
number 0:not
active
1:active
rtl1,sev
Reserve time low severity
x x
text “MAJ”,
“MIN” , or “RO"
rtll,thr
Reserve time low threshold
x x
number 0-99.9 hours
vla1,acc
Very low voltage relay
x x
text “R1” ,“R2”, “R3”, R4, or “”
vla1,ast
Very low voltage alarm state
x
number 0:not
active
1:active
vla1,sev
Very low voltage severity
x x
text “MAJ”,“MIN” , or “RO"
vla1,thr
Very low voltage threshold
x x
number 40-51:46V
amtl1,acc Low ambient temp relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
amtl1,ast
Low ambient temp alarm state
x
number 0:not
active
1:active
amtl1,sev Low ambient temp severity
x x
text “MAJ”,
“MIN” , or “RO"
amtl1,thr
Low ambient temp threshold
x x
number -40-10:-40C
amth1,acc High ambient temp relay
x x
text
“R1” ,“R2”, “R3”, “R4”, or “”
amth1,ast High ambient temp alarm state
x
number 0:not
active
1:active
amth1,sev High ambient temp severity
x x
text “MAJ”,
“MIN” , or “RO"
amth1,thr High ambient temp threshold
x x
number 35-75:75C