22-position external distribution panel
Overview
The J5694722 external distribution accepts up to 22 bullet-breakers for DC loads and
occupies 3U of vertical rack space in a 23î rack. The panel has a total output capacity of
400A and is front accessible. The following configurations are available in 3 distinct
distribution modules:
•
Without contactor
•
With 400A LVLD and 500A shunt
•
With 400A LVBD and 500A shunt
Features
Figure 12-7: J5694722 External Distribution
•
Up to 22 flexible battery positions that can be configured either with the battery bus or
the load bus using an adapter plate
•
All lug connections shall accept double-holed lugs.
•
Staggered vertical arrangement of up to three distributions directly stacked with wiring
access.
•
Contactor control, measurements and alarms with the QS84x compatible ES772 module
•
CO ground connection
•
Contactor options ñ None, LVBD, LVLD
•
500A shunt
•
Accommodates single, double and triple pole breakers with lug adapter for multi-pole
breakers
•
English hardware (1/4-20) for all customer connections
•