GE Industrial Solutions CPS6000 User Manual
Page 105

CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
105
Boost: The Boost function allows battery charging to be expedited by raising the system
voltage to Boost level for a set time. The following boost mode parameters are set in this area
of the menu system:
Set Point
Boost voltage (set point) is adjustable from 48.0V to 58.0V in 0.1V
increments. The factory default setting is 55.2V.
Voltage Alarms
High voltage alarm thresholds in effect while the system is in boost mode.
The Very High Major alarm triggers shutdown of the faulty rectifier(s).
This threshold can be set from 50V to 60V. The factory default setting is
58.0V.
The High Minor alarm does not force rectifiers to shut down. The threshold
can be set from 50 to 60V. The factory default setting is 56V.
Max Duration
Duration the system can remain in boost mode can be set from 1 to 80
hours. The factory default setting is 1 hour.
Automatic
Enable or disable the automatic boost feature.
The factory default is
disabled.
System Settings: Menus for configuring the following system parameters:
Display Contrast
Allows display backlight intensity to be adjusted for contrast in
local ambient light. Factory default is 50%.
System Date and
Time
Set date in yyyy-mm-dd and time in hh:mm:ss format.
Daylight Savings
Enable or disable. Factory default is Enabled.
Display T Units
Display temperature status in C or °F. Factory default is C.
High Ambient T
High temperature alarm threshold that can be set from 35°C to
75°C. The factory default setting is 75°C.
Low Ambient T
Low temperature alarm threshold that can be set from -40°C to
10°C. The factory default setting is -40°C.
Communication Ports: Menus for configuring the following communication parameters:
Port Type
Set the communication port to either Local or Modem. Factory
default is Local.
Local Port Settings
Enable or disable Write Access, the ability to change system
settings through the local port. The factory default setting is
enabled.
Set the port Baud Rate to auto, 2400, 4800, 9600 or 19200. The
factory default setting is auto.
Set port Flow Control to none, HW (hardware) or SW (software).
The factory default setting is none.