GE Industrial Solutions CPS6000 User Manual
Page 184

CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
184
login Log-in
Syntax:
login “password”
where password is either the user, super-user or administrator password
Description
This command is used to log-in as a user, super-user or administrator. For example, if you are
currently logged into the controller as a user but would like to change the site id you must first
use this command to log-in as a super-user. You must be logged in as an administrator in order
to upgrade the software and change passwords.
ope
Operate a Control
Syntax:
ope obj,attr=value
where: obj,attr is an object-attribute pair. For example, dc1,pbt.
Description
This command is used to operate a system control parameter. Examples are listed below to
illustrate how this command works.
ope ps1,usl=1Update serial link
ope dc1,stt="boost"Place plant into boost mode
You must be logged in as a super-user to use this command.
pas Change
Passwords
Syntax:
pas t,“password”,“password”
where “t” is to change the user password, “s” to change the super-user password,
and “a” to change the administrator password. password is the new password
Description
This command changes either the user or super-user password. You must be logged in as a
super-user to use this command. The password is sent twice in order to avoid mistakes. The
password must have at least 6 characters but no more than 15 characters.
You must be logged in as a super-user to use this command.