GE Industrial Solutions CPS6000 User Manual
Page 104

CPS6000 –48V Indoor/Outdoor Power Shelf
Issue 21 January 2008
104
Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec
• LVLD2 (Disabled)
Disconnect Mode (Voltage); Range: Voltage, Voltage+Time
Disconnect Voltage (442.0V); Range: 39-50V
Time Delay (0 min); Range: 0-300min
Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec
• LVLD3 (Disabled)
Disconnect Mode (Voltage); Range: Voltage, Voltage+Time
Disconnect Voltage (42.0V); Range: 39-50V
Time Delay (0 min); Range: 0-300min
Reconnect Mode (Voltage); Range: Voltage, Voltage+Time
Reconnect Voltage (44.0V); Range: 39-55V
Time Delay (0 sec); Range: 0-300sec
Shutdown Alarm: The Shutdown Alarm occurs when system shutdown due to a battery
disconnect is imminent. The alarm can be enabled or disabled, and has a factory default
threshold setting of 42.0V based upon the LVBD. The alarm is issued based on the lower
disconnect threshold of the multiple contactors. This feature is factory Disabled.
Ringers: Ringer modules are an option for the CPS6000. The QS840A has the ability to
manage two ringer chassis. Configuration for the ringer settings are shown below.
Voltage
Nominal ringer output AC voltage. Range 65-100 VAC
rms
. Factory
default is 100.
Frequency
Nominal ringer output frequency. Range 15-50 Hz. Factory default is
20.
DC Offset
Enable or Disable the capability of configuring a DC offset voltage to
the Ring Output. The factory default setting is Enabled.
Redundancy
Enable or disable the loss of redundancy alarm. Alarms when one of the
two ringer modules installed in the ringer chassis is lost.