Installation guide, E8950 – Veris Industries E8950 Install User Manual
Page 83

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 83
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
APPENDIX 3: QUICK GUIDE TO CALCULATE THE NUMBER OF METERS SUPPORTED
The E8950 can support up to 32 meters (maximum) and up to 1000 total BACnet points.
The installer can mix meter types, but only from the list of supported meters.
Set all meters to a common baud rate. The combined number of points (see table below) must not exceed 1000.
Meter Type
Modbus Addresses
per Meter
BACnet Points per
Address
Total Number of
Points per Meter
Maximum
number of Meters
Supported
E30Ax42
1
783
783
1
E30Bx42
1
446
446
2
E30Cx42
1
446
446
2
E30Ax84
2
783
1566
0
E30Bx84
2
446
892
1
E30Cx84
2
446
892
1
E31A42
2
783
1566
0*
E31B42
2
446
892
1
E31C42
2
446
892
1
E31A84
2
783
1566
0
E31B84
2
446
892
1
E31C84
2
446
892
1
E50C2
1
63
63
15
E50C3
1
63
63
15
E51C2
1
94
94
10
E51C3
1
94
94
10
H8035
1
3
3
32**
H8036
1
28
28
32**
H8163-CB
1
54
54
18
H8238
8
73
584
1
H8436
1
34
34
29
H8437
1
66
66
15
* The E31A42 can be configured with help from Veris Customer Support.
** 32 meters maximum.