Installation guide, E8950 – Veris Industries E8950 Install User Manual
Page 57

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 57
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Voltage 1 Alarm Status
Write 0 to alarm bits to
clear alarms
AV160
n/a
1
241
Latching Alarms are cleared by writing a 0 to its alarm bit. Writing to a
Non-Latching alarm is ignored
Bit 0: High Latching Alarm
Bit 1: Low Latching Alarm
Bit 2-7: Reserved for future use (reads 0)
Bit 8: High Non-Latching Alarm
Bit 9: Low Non-Latching Alarm
Bit 10-15: Reserved for future use (reads 0)
Voltage 2 Alarm Status
Write 0 to alarm bits to
clear alarms
AV161
n/a
1
242
Latching Alarms are cleared by writing a 0 to its alarm bit. Writing to a
Non-Latching alarm is ignored
Bit 0: High Latching Alarm
Bit 1: Low Latching Alarm
Bit 2-7: Reserved for future use (reads 0)
Bit 8: High Non-Latching Alarm
Bit 9: Low Non-Latching Alarm
Bit 10-15: Reserved for future use (reads 0)
Voltage 3 Alarm Status
Write 0 to alarm bits to
clear alarms
AV162
n/a
1
243
Latching Alarms are cleared by writing a 0 to its alarm bit. Writing to a
Non-Latching alarm is ignored
Bit 0: High Latching Alarm
Bit 1: Low Latching Alarm
Bit 2-7: Reserved for future use (reads 0)
Bit 8: High Non-Latching Alarm
Bit 9: Low Non-Latching Alarm
Bit 10-15: Reserved for future use (reads 0)
Power Up Counter
Power Up Counter
AV163
n/a
1
531
Number of power-up cycles (write 0 to reset)
User Defined Status
Register
1 in bit 0 enables CT
phase assignment
AV164
n/a
1
62017
User Defined Status Register:
Bit 0: Enable User CT Phase Assignment
Bit 1-15: Reserved
Voltage Phase for Branch
Channel 1
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV165
n/a
1
62116
Voltage Phase for Branch
Channel 2
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV166
n/a
1
62117
Voltage Phase for Branch
Channel 3
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV167
n/a
1
62118
Voltage Phase for Branch
Channel 4
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV168
n/a
1
62119
Voltage Phase for Branch
Channel 5
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV169
n/a
1
62120
Voltage Phase for Branch
Channel 6
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV170
n/a
1
62121
Voltage Phase for Branch
Channel 7
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV171
n/a
1
62122
Voltage Phase for Branch
Channel 8
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV172
n/a
1
62123
Voltage Phase for Branch
Channel 9
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV173
n/a
1
62124
Voltage Phase for Branch
Channel 10
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV174
n/a
1
62125
Voltage Phase for Branch
Channel 11
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV175
n/a
1
62126
Voltage Phase for Branch
Channel 12
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV176
n/a
1
62127
Voltage Phase for Branch
Channel 13
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV177
n/a
1
62128
E30A042 and E30A142x Branch Circuit Power Meter, cont.