Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Peak Real Energy Demand
Largest value recorded
AI26
kW
1
309/310
The peak demand is the highest demand value (register 26)
that has occurred. This value is also displayed on LCD for MAX
kW when the comms board is present.
Present Reactive Energy Sub-
Interval
SubInterval value currently
accumulating
AI27
KVAR
1
311/312
Present kVAR Sub-Interval. This is the currently accumulating
Sub-Interval KVAR, which is constantly changing.
Present Reactive Energy Demand Most recent Demand Sub-
Interval
AI28
KVAR
1
313/314
Present kVAR. This is the present kVar, which is updated at
the end of every sub-interval. This value is the average of
the previous N sub-intervals, where N is the number of sub-
intervals (register 37).
Peak Reactive Energy Demand
Largest value recorded
AI29
KVAR
1
315/316
Peak kVar. The peak kVar is the highest kVar value (register 28)
that has occurred.
Count of KWh resets
# of times kWh accumulator
was reset
AI30
n/a
1
31
Count of KWh resets. The number of times the peak demand
(register 27) has been reset. This value rolls over from 65535
to zero.
Count of Peak Demand Resets
# of times Peak kW Demand
was reset
AI31
n/a
1
32
Count of Peak Demand Resets. The number of times the peak
demand (register 27) has been reset. This value rolls over
from 65535 to zero.
Count of Peak kVAR Resets
# of times Peak kVAR Demand
was reset
AI32
n/a
1
33
Count of Peak kVar Resets. The number of times the peak kVar
(register 30) has been reset. This value rolls over from 65535
to zero.
Count of Elapsed Sub Intervals
Sub-intervals filled in current
Block
AI33
n/a
1
34
Count of Elapsed Sub Intervals. This counts the number
of subintervals that have elapsed. Because the demand
(register 28) is updated every sub-interval, this register may
be read to determine if an identical value in register 28 is
actually the same demand
# of Readings in Present sub-
interval
updated every 200 mS
AI34
n/a
5000
35
Number readings in present sub-interval. This value indicates
the number of readings that are represented by the present
subinterval (register 25). This register acts as an unsigned
integer. Values larger than 32767 should not be “trusted”.
See below for explanation of sub-interval reading count
overflow. This register will increment every 200 ms (5 times
per Second).
System ID
15024=Basic, 15025=Enhanced AI35
n/a
0
38
System ID. This register reads as 15024 for the Basic Meter and
15025 for the Enhanced Model to help identify the meter.
CT Size
Primary Rating, in Amps
AI36
n/a
0
39
CT Size. This register reads as the CT size: 100, 300, etc.
CT Number
Qty of CTs configured
AI37
n/a
0
40
CT Number. The number of CTs that are connected, 1,2, or 3.
Count of Phase Losses.
# of times phase loss has
occurred
AI38
n/a
1
43
Count of Phase Losses. The number of times a phase loss has
occurred on any phase. This value rolls over from 65535 to
zero.
H8163 Series Energy Meter with H8163-CB Modbus Communication Board, cont.