Installation guide, Installation, Product diagram – Veris Industries E8950 Install User Manual

Page 3: Led blink codes

background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 3

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

2. Connect the Modbus outputs of the devices to the Modbus side of the E8950.

+

S

E8950

Meters

120 Ω resistor on the last device in the daisy chain.

• Wire the RS-485 bus as a daisy chain from device to device (up to 32

supported devices) without any stubs. Use a 120 Ω termination resistor
(not included) on the device farthest from the E8950. An additional 120 Ω
termination and Modbus line polarization are provided internal to the
E8950.

• Connect shield to earth ground somewhere on the RS-485 bus. The shield

is not internally connected to earth ground.

• Use wire with an insulation rating sufficient for the location where the

meter is installed (e.g. Belden 1120A for installation in panels with up to
600 VAC).

3. Connect 9-30 VDC or 12-24 VAC to the +PWR/-PWR terminals of the 6-pin

connector.

Modbus Setup

Use DIP switches S0 to S2 to set the Modbus baud rate to 9600, 19200, or 38400. The
default baud rate is 9600, because this rate is available on all the devices supported
by the E8950. If all connected devices support a faster rate, use the highest rate in
common to improve performance. Set the E8950 and all Modbus
devices in the series to the same rate.
Set all devices to NO parity.

Baud Rate

S0 – S2 DIP Switches

S0

S1

S2

9600 Baud

19200 Baud

38400 Baud

BACnet Physical Layer Selection

Use DIP switch A7 to select the BACnet physical layer. See
Appendix 2: DIP Switch Addresses section at the back of this
document for physical layer switch settings.

Layer

Switch Position

BACnet/IP

BACnet MS/TP

INSTALLATION

The E8950 can be DIN rail mounted, using the supplied DIN rail mounting clip, or
screw-mounted directly to a wall or other flat surface using the mounting holes on
either side of the housing.

6 Pin Connector

Pin #

Pin Assignment

Pin 1

RS-485 + (Modbus)

Pin 2

RS-485 - (Modbus)

Pin 3

RS-485 GND

Pin 4

V +

Pin 5

V -

Pin 6

FRAME GND

1. Refer to the Installation Guides for the specific meter devices used to locate

instructions on connecting the meters and changing the configuration settings.

Modbus

Power

PRODUCT DIAGRAM

BACnet MS/TP RS-485

DIP switches for setting MS/TP

MAC address, physical interface

type, MS/TP baud rate, Modbus

baud rate, and enabling auto-

discovery of meters

BACnet
IP/Ethernet
Port

Modbus RTU port RS-485 +, -, Shield

Power 9-30 VDC, 12-24 VAC

LED BLINK CODES

LED

Color

Description

SPL

Blue

Reserved for future use. It may be on or off when the unit is on.

RUN

Dark Green

Slow blink (one second on, one second off) after the product

has initialized (approximately 40 seconds after the unit is

powered or reset). This indicates normal operation.

ERR

Red

• This illuminates blink briefly when the Run LED first comes on

(about 15 seconds after the unit is powered or reset).

• A steady red light indicates the unit needs attention.

RX

Yellow

Indicates the device is receiving data on the Modbus link.

TX

Orange

Indicates the device is transmitting data on the Modbus link.

PWR

Light Green

This is always on when the unit is powered.