beautypg.com

Installation guide, E8950 – Veris Industries E8950 Install User Manual

Page 59

background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 59

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Voltage Phase for Branch

Channel 40

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV204

n/a

1

62155

Voltage Phase for Branch

Channel 41

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV205

n/a

1

62156

Voltage Phase for Branch

Channel 42

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV206

n/a

1

62157

Voltage Phase for Aux

Channel 1

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV207

n/a

1

62158

Voltage Phase for Aux

Channel 2

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV208

n/a

1

62159

Voltage Phase for Aux

Channel 3

0=phase-1/A, 1=phase-

2/B, 2=phase-3/C

AV209

n/a

1

62160

Analog_Output objects:
AUX Resets: Write value

to reset

10203=kWh,

29877=Max Current &

Max kW

AO1

n/a

1

294

Write the listed value to perform the corresponding reset:
10203 = Clear kWh value to zero
29877 = Clear Max Current and Max kW values to zero

Global Resets: Write

value to reset

10203=kWh, others…

AO2

n/a

1

295

Write the listed value to perform the corresponding reset:
26012 = Begin new Demand Sub-interval
26013 = Reset Demand
31010 = Reset all Latching Alarms
10203 = Clear all kWh values to zero
29877 = Clear all Max Current and Max kW values to zero
20097 = Clear all Max Demand values to zero

Channel 1 Reset

10203=kWh,

29877=Max Current &

Max kW

AO3

n/a

1

1126

Write the listed value to perform the corresponding reset:
10203 = Clear kWh value to zero
29877 = Clear Max Current and Max kW values to zero

Channel 2 Reset

10203=kWh,

29877=Max Current &

Max kW

AO4

n/a

1

1127

Channel 3 Reset

10203=kWh,

29877=Max Current &

Max kW

AO5

n/a

1

1128

Channel 4 Reset

10203=kWh,

29877=Max Current &

Max kW

AO6

n/a

1

1129

Channel 5 Reset

10203=kWh,

29877=Max Current &

Max kW

AO7

n/a

1

1130

Channel 6 Reset

10203=kWh,

29877=Max Current &

Max kW

AO8

n/a

1

1131

Channel 7 Reset

10203=kWh,

29877=Max Current &

Max kW

AO9

n/a

1

1132

Channel 8 Reset

10203=kWh,

29877=Max Current &

Max kW

AO10

n/a

1

1133

Channel 9 Reset

10203=kWh,

29877=Max Current &

Max kW

AO11

n/a

1

1134

Channel 10 Reset

10203=kWh,

29877=Max Current &

Max kW

AO12

n/a

1

1135

E30A042 and E30A142x Branch Circuit Power Meter, cont.