Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Voltage Phase for Branch
Channel 40
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV204
n/a
1
62155
Voltage Phase for Branch
Channel 41
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV205
n/a
1
62156
Voltage Phase for Branch
Channel 42
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV206
n/a
1
62157
Voltage Phase for Aux
Channel 1
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV207
n/a
1
62158
Voltage Phase for Aux
Channel 2
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV208
n/a
1
62159
Voltage Phase for Aux
Channel 3
0=phase-1/A, 1=phase-
2/B, 2=phase-3/C
AV209
n/a
1
62160
Analog_Output objects:
AUX Resets: Write value
to reset
10203=kWh,
29877=Max Current &
Max kW
AO1
n/a
1
294
Write the listed value to perform the corresponding reset:
10203 = Clear kWh value to zero
29877 = Clear Max Current and Max kW values to zero
Global Resets: Write
value to reset
10203=kWh, others…
AO2
n/a
1
295
Write the listed value to perform the corresponding reset:
26012 = Begin new Demand Sub-interval
26013 = Reset Demand
31010 = Reset all Latching Alarms
10203 = Clear all kWh values to zero
29877 = Clear all Max Current and Max kW values to zero
20097 = Clear all Max Demand values to zero
Channel 1 Reset
10203=kWh,
29877=Max Current &
Max kW
AO3
n/a
1
1126
Write the listed value to perform the corresponding reset:
10203 = Clear kWh value to zero
29877 = Clear Max Current and Max kW values to zero
Channel 2 Reset
10203=kWh,
29877=Max Current &
Max kW
AO4
n/a
1
1127
Channel 3 Reset
10203=kWh,
29877=Max Current &
Max kW
AO5
n/a
1
1128
Channel 4 Reset
10203=kWh,
29877=Max Current &
Max kW
AO6
n/a
1
1129
Channel 5 Reset
10203=kWh,
29877=Max Current &
Max kW
AO7
n/a
1
1130
Channel 6 Reset
10203=kWh,
29877=Max Current &
Max kW
AO8
n/a
1
1131
Channel 7 Reset
10203=kWh,
29877=Max Current &
Max kW
AO9
n/a
1
1132
Channel 8 Reset
10203=kWh,
29877=Max Current &
Max kW
AO10
n/a
1
1133
Channel 9 Reset
10203=kWh,
29877=Max Current &
Max kW
AO11
n/a
1
1134
Channel 10 Reset
10203=kWh,
29877=Max Current &
Max kW
AO12
n/a
1
1135