Installation guide, E8950 – Veris Industries E8950 Install User Manual
Page 76

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 76
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Branch 31 Alarm Status
Write 0 to alarm bits to
clear alarms
AV139
n/a
1
208
Branch 32 Alarm Status
Write 0 to alarm bits to
clear alarms
AV140
n/a
1
209
Branch 33 Alarm Status
Write 0 to alarm bits to
clear alarms
AV141
n/a
1
210
Branch 34 Alarm Status
Write 0 to alarm bits to
clear alarms
AV142
n/a
1
211
Branch 35 Alarm Status
Write 0 to alarm bits to
clear alarms
AV143
n/a
1
212
Branch 36 Alarm Status
Write 0 to alarm bits to
clear alarms
AV144
n/a
1
213
Branch 37 Alarm Status
Write 0 to alarm bits to
clear alarms
AV145
n/a
1
214
Branch 38 Alarm Status
Write 0 to alarm bits to
clear alarms
AV146
n/a
1
215
Branch 39 Alarm Status
Write 0 to alarm bits to
clear alarms
AV147
n/a
1
216
Branch 40 Alarm Status
Write 0 to alarm bits to
clear alarms
AV148
n/a
1
217
Branch 41 Alarm Status
Write 0 to alarm bits to
clear alarms
AV149
n/a
1
218
Branch 42 Alarm Status
Write 0 to alarm bits to
clear alarms
AV150
n/a
1
219
AUX Channel (phase 1)
Alarm Status
Write 0 to alarm bits to
clear alarms
AV151
n/a
1
220
AUX Channel (phase 2)
Alarm Status
Write 0 to alarm bits to
clear alarms
AV152
n/a
1
221
AUX Channel (phase 3)
Alarm Status
Write 0 to alarm bits to
clear alarms
AV153
n/a
1
222
AUX Channel (Neutral)
Alarm Status
Write 0 to alarm bits to
clear alarms
AV154
n/a
1
223
Overvoltage Alarm Timer Alarm event duration
threshold
AV155
Seconds
1
236
Not used on E3xCxxx models; reports QNAN
Controls entry into Overvoltage alarm state. A return to a non-alarm
state is instantaneous. All channels use these same global timers.
Note that the parameter measurement update rate is 1.6 sec, which
limits the effective resolution of these timers.
Undervoltage Alarm
Timer
Alarm event duration
threshold
AV156
Seconds
1
237
Not used on E3xCxxx models; reports QNAN
Controls entry into Undervoltage alarm state. A return to a non-alarm
state is instantaneous. All channels use these same global timers.
Note that the parameter measurement update rate is 1.6 sec, which
limits the effective resolution of these timers.
Overvoltage Alarm
Threshold
Overvoltage level
threshold (0=OFF)
AV157
Volts
5
238
Not used on E3xCxxx models; reports QNAN
Undervoltage Alarm
Threshold
Undervoltage level
threshold (0=OFF)
AV158
Volts
5
239
Not used on E3xCxxx models; reports QNAN
Voltage Alarm Hysteresis Voltage Alarm Hysteresis
(% of setpoint)
AV159
Percent
1
240
Not used on E3xCxxx models; reports QNAN Percentage of setpoint
E30Bxxx/Cxxx and E31Bxxx/Cxxx Branch Circuit Meters cont.