Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

kW: Min

Minimum Real Power since last

reset

AI27

kW

1

311/312

kW: Max

Maximum Real Power since

last reset

AI28

kW

1

313/314

Firmware Revision - Reset

System

Firmware Revision - Reset

System

AI29

n/a

0

43

Firmware Revision - Operating

System

Firmware Revision - Operating

System

AI30

n/a

0

44

Serial number MSW

MSW of unsigned-long integer

AI31

n/a

0

45

Serial number LSW

LSW of unsigned-long integer

AI32

n/a

0

46

Error Register

0=no error; 1=NV Ram error;

others rsvd

AI33

n/a

0

47

Reports internal errors detected by the microcontroller.

The ALIVE LED is steadily lit (not blinking) if any errors are

detected.

Device ID

15027=8-meter config;

15027=6-meter

AI34

n/a

0

48

Meter Alarm Status (non-

latching)

bitmap of 8 alarms - bits 9-15

are all 0

AI35

n/a

0

49

Holds the instantaneous state of the meter alarms. The

bits in this register are only set while the alarm condition

exists. These alarms cannot be reset by the user. Only set

the Over Voltage Alarm when its time-delay condition is

satisfied (see AV4).

bit 0 = over current
bit 1 = under current
bit 2 = over kVA
bit 3 = under kVA
bit 4 = over voltage
bit 5 = under voltage
bit 6 = phase loss A
bit 7 = phase loss B
bit 8 = phase loss C
bits 9-15 = 0

Over Voltage Set Counter

Over Voltage Set Counter

AI36

n/a

0

50

Over Voltage Reset Counter

Over Voltage Reset Counter

AI37

n/a

0

51

Under Voltage Set Counter

Under Voltage Set Counter

AI38

n/a

0

52

Under Voltage Reset Counter

Under Voltage Reset Counter

AI39

n/a

0

53

Phase Loss A Set Counter

Phase Loss A Set Counter

AI40

n/a

0

54

Phase Loss A Reset Counter

Phase Loss A Reset Counter

AI41

n/a

0

55

Phase Loss B Set Counter

Phase Loss B Set Counter

AI42

n/a

0

56

Phase Loss B Reset Counter

Phase Loss B Reset Counter

AI43

n/a

0

57

Phase Loss C Set Counter

Phase Loss C Set Counter

AI44

n/a

0

58

Phase Loss C Reset Counter

Phase Loss C Reset Counter

AI45

n/a

0

59

Over Current Set Counter

Over Current Set Counter

AI46

n/a

0

60

Over Current Reset Counter

Over Current Reset Counter

AI47

n/a

0

61

Under Current Set Counter

Under Current Set Counter

AI48

n/a

0

62

Under Current Reset Counter

Under Current Reset Counter

AI49

n/a

0

63

Over kVA Set Counter

Over kVA Set Counter

AI50

n/a

0

64

Over kVA Reset Counter

Over kVA Reset Counter

AI51

n/a

0

65

Under kVA Set Counter

Under kVA Set Counter

AI52

n/a

0

66

Under kVA Reset Counter

Under kVA Reset Counter

AI53

n/a

0

67

Modbus addr as conf by DIP

switches

integer value (1-247) addr of

1st meter

AI54

n/a

0

68

H8238 Series Multi-Circuit Meters (H8238, H8238E & H8238EL), cont.