Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Meter Name: First 2 characters
First 2 ASCII characters
(Default=MT)
AV12
n/a
0
39
AV12 – AV15 is a decimal representation of two ASCII
characters used for the meter name. Allowed characters
are 21h through 7Dh, excluding 5Ch. The high order byte
is the high-order character.
For example:
AV12 Present Value = 19796 4D54 (hex)
M = 4D (hex)
T = 54 (hex)
Meter Name: Second 2
characters
Second 2 ASCII characters
(Default=Rx)
AV13
n/a
0
40
Board Name: First 2 characters
First 2 ASCII characters
(Default=BR)
AV14
n/a
0
41
Board Name: Second 2
characters
Second 2 ASCII characters
(Default=C1)
AV15
n/a
0
42
Meter Enable Register
bitmap of 8 meters: 0=off;
1=on; 9-15=0
AV16
n/a
0
73
Meter Enable Register: allows the user to enable or disable
selected meters on the board. A disabled meter will not
respond to any Modbus queries. A 1 indicates an enabled
meter; a 0 indicates a disabled meter. This register can
only be written to meter #1. When read from meters 2
through 8, the high bit (bit 15) is always set as a flag that
the register may not be written to that meter. When in
6-meter mode, bit 6 and bit 7 may not be set and will
always read as 0.
bit 0 = Meter #1 (always reads as 1, cannot be reset)
bit 1 = Meter #2
bit 2 = Meter #3
bit 3 = Meter #4
bit 4 = Meter #5
bit 5 = Meter #6
bit 6 = Meter #7
bit 7 = Meter #8
bits 8-14 = 0
bit 15 = 0 if read from Meter #1; 1 if read from Meters
#2-#8
Critical Alarm Register
info only: set 0=critical; 1=not;
9-15=0
AV17
n/a
0
74
Critical Alarm Register: allows the user to indicate which
of the meter’s alarms are critical and non-critical. This
product takes no action on the contents of this register.
It is provided for monitoring systems’ use. A 1 indicates a
critical alarm; a 0 indicates a non-critical alarm.
bit 0 = over current
bit 1 = under current
bit 2 = over kVA
bit 3 = under kVA
bit 4 = over voltage
bit 5 = under voltage
bit 6 = phase loss A
bit 7 = phase loss B
bit 8 = phase loss C
bits 9-15 = 0
H8238 Series Multi-Circuit Meters (H8238, H8238E & H8238EL), cont.