Installation guide, E8950 – Veris Industries E8950 Install User Manual
Page 31

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 31
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
E30A042 and E30A142 Branch Circuit Power Meter
The E30A042 and E30A142 meters have 783 data objects per Modbus address and operate at 9600, 19200, or 38400 baud. These meters monitor current, power, demand, and
energy on 42 branch circuits and 4 main circuits (up to 3 phases, plus neutral) and use only one Modbus address.
Due to the capacity limitation of 1000 BACnet data points, the E30Ax84 models and the E31Axxx models are not fully supported. If these products are discovered by the E8950,
they will be automatically mapped to the E30Bxxx profile, which supports a more limited data set.
AV4-AV45 are not writable on E30xxxx solid-core models because the CT size is fixed (at 100 A). Other values written revert to 100 A the next time the meter is scanned.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Analog_Input objects
Frequency: (derived from
Phase A)
Frequency (derived from
Phase A)
AI1
Hz
0.01
600/601
VOLTS L-N: 3ph Ave
Voltage L-L - average of
active phases
AI2
Volts
5
602/603
VOLTS L-L: 3ph Ave
Voltage L-N - average of
active phases
AI3
Volts
5
604/605
VOLTS A-N
Instantaneous Voltage
Ph-A to Neutral
AI4
Volts
5
606/607
VOLTS B-N
Instantaneous Voltage
Ph-B to Neutral
AI5
Volts
5
608/609
VOLTS C-N
Instantaneous Voltage
Ph-C to Neutral
AI6
Volts
5
610/611
VOLTS A-B
Instantaneous Voltage
Phase A to B
AI7
Volts
5
612/613
VOLTS B-C
Instantaneous Voltage
Phase B to C
AI8
Volts
5
614/615
VOLTS A-C
Instantaneous Voltage
Phase A to C
AI9
Volts
5
616/617
kWh Energy: 3ph Total
Real Energy - total of
active phases
AI10
kWh
0
618/619
kW: 3ph Total
Inst Real Power- total of
active phases
AI11
kW
1
620/621
Power Factor: 3ph Total
Inst Power Factor -
average of phases
AI12
PF
0.01
622/623
Amps: 3ph Average
(phases 1,2,3)
Inst Current- average of
active phases
AI13
Amps
5
624/625
kW: Phase 1
Instantaneous Real
Power - Phase 1
AI14
kW
1
626/627
kW: Phase 2
Instantaneous Real
Power - Phase 2
AI15
kW
1
628/629
kW: Phase 3
Instantaneous Real
Power - Phase 3
AI16
kW
1
630/631
Power Factor: Phase 1
Instantaneous Power
Factor - Phase A
AI17
PF
0.01
632/633
Power Factor: Phase 2
Instantaneous Power
Factor - Phase B
AI18
PF
0.01
634/635
Power Factor: Phase 3
Instantaneous Power
Factor - Phase C
AI19
PF
0.01
636/637
Amps: Phase 1
Instantaneous Current -
Phase 1
AI20
Amps
5
638/639
Amps: Phase 2
Instantaneous Current -
Phase 2
AI21
Amps
5
640/641
Amps: Phase 3
Instantaneous Current -
Phase 3
AI22
Amps
5
642/643