Installation guide, E8950 – Veris Industries E8950 Install User Manual
Page 62

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 62
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
E30Bxxx/Cxxx and E31Bxxx/Cxxx Branch Circuit Meters
The E3xBxxx/Cxxx meters have 446 data objects per Modbus address and operate at 9600, 19200 or 38400 baud. These meters monitor current on 42 branch circuits and 4
main circuits (up to 3 phases, plus neutral) for each Modbus address. The E3xBxxx models also monitor power, demand, and energy on the main channels (not the branches).
The E30Bx42/Cx42 models have one Modbus address and support only 42 branch channels (plus main channels). The E30Bx84/Cx84 models and all E31Bxxx/Cxxx models have
two Modbus addresses and support up to 84 branch channels and two sets of main channels. On E3xCxxx models, some of the data objects are not used and will return QNAN
when their Present_Value is read.
AV4-AV45 are not writable on E30Bxxx/E30Cxxx solid-core models because the CT size is fixed (at 100 A). Other values written revert to 100 A the next time the meter is
scanned. AV4-AV45 are writable on E31Bxxx/E31Cxxx split-core models.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Analog_Input objects
Frequency: (derived from
Phase A)
Frequency (derived from
Phase A)
AI1
Hz
0.01
600/601
Not used on E3xCxxx models; reports QNAN
VOLTS L-N: 3ph Ave
Voltage L-L - average of
active phases
AI2
Volts
5
602/603
Not used on E3xCxxx models; reports QNAN
VOLTS L-L: 3ph Ave
Voltage L-N - average of
active phases
AI3
Volts
5
604/605
Not used on E3xCxxx models; reports QNAN
VOLTS A-N
Instantaneous Voltage
Ph-A to Neutral
AI4
Volts
5
606/607
Not used on E3xCxxx models; reports QNAN
VOLTS B-N
Instantaneous Voltage
Ph-B to Neutral
AI5
Volts
5
608/609
Not used on E3xCxxx models; reports QNAN
VOLTS C-N
Instantaneous Voltage
Ph-C to Neutral
AI6
Volts
5
610/611
Not used on E3xCxxx models; reports QNAN
VOLTS A-B
Instantaneous Voltage
Phase A to B
AI7
Volts
5
612/613
Not used on E3xCxxx models; reports QNAN
VOLTS B-C
Instantaneous Voltage
Phase B to C
AI8
Volts
5
614/615
Not used on E3xCxxx models; reports QNAN
VOLTS A-C
Instantaneous Voltage
Phase A to C
AI9
Volts
5
616/617
Not used on E3xCxxx models; reports QNAN
kWh Energy: 3ph Total
Real Energy - total of
active phases
AI10
kWh
0
618/619
Not used on E3xCxxx models; reports QNAN
kW: 3ph Total
Inst Real Power- total of
active phases
AI11
kW
1
620/621
Not used on E3xCxxx models; reports QNAN
Power Factor: 3ph Total
Inst Power Factor -
average of phases
AI12
PF
0.01
622/623
Not used on E3xCxxx models; reports QNAN
Amps: 3ph Average
(phases 1,2,3)
Inst Current- average of
active phases
AI13
Amps
5
624/625
kW: Phase 1
Instantaneous Real
Power - Phase 1
AI14
kW
1
626/627
Not used on E3xCxxx models; reports QNAN
kW: Phase 2
Instantaneous Real
Power - Phase 2
AI15
kW
1
628/629
Not used on E3xCxxx models; reports QNAN
kW: Phase 3
Instantaneous Real
Power - Phase 3
AI16
kW
1
630/631
Not used on E3xCxxx models; reports QNAN
Power Factor: Phase 1
Instantaneous Power
Factor - Phase A
AI17
PF
0.01
632/633
Not used on E3xCxxx models; reports QNAN
Power Factor: Phase 2
Instantaneous Power
Factor - Phase B
AI18
PF
0.01
634/635
Not used on E3xCxxx models; reports QNAN
Power Factor: Phase 3
Instantaneous Power
Factor - Phase C
AI19
PF
0.01
636/637
Not used on E3xCxxx models; reports QNAN
Amps: Phase 1
Instantaneous Current -
Phase 1
AI20
Amps
5
638/639
Amps: Phase 2
Instantaneous Current -
Phase 2
AI21
Amps
5
640/641