beautypg.com

Installation guide, E8950 – Veris Industries E8950 Install User Manual

Page 62

background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 62

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

E30Bxxx/Cxxx and E31Bxxx/Cxxx Branch Circuit Meters

The E3xBxxx/Cxxx meters have 446 data objects per Modbus address and operate at 9600, 19200 or 38400 baud. These meters monitor current on 42 branch circuits and 4
main circuits (up to 3 phases, plus neutral) for each Modbus address. The E3xBxxx models also monitor power, demand, and energy on the main channels (not the branches).
The E30Bx42/Cx42 models have one Modbus address and support only 42 branch channels (plus main channels). The E30Bx84/Cx84 models and all E31Bxxx/Cxxx models have
two Modbus addresses and support up to 84 branch channels and two sets of main channels. On E3xCxxx models, some of the data objects are not used and will return QNAN
when their Present_Value is read.

AV4-AV45 are not writable on E30Bxxx/E30Cxxx solid-core models because the CT size is fixed (at 100 A). Other values written revert to 100 A the next time the meter is
scanned. AV4-AV45 are writable on E31Bxxx/E31Cxxx split-core models.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Analog_Input objects
Frequency: (derived from

Phase A)

Frequency (derived from

Phase A)

AI1

Hz

0.01

600/601

Not used on E3xCxxx models; reports QNAN

VOLTS L-N: 3ph Ave

Voltage L-L - average of

active phases

AI2

Volts

5

602/603

Not used on E3xCxxx models; reports QNAN

VOLTS L-L: 3ph Ave

Voltage L-N - average of

active phases

AI3

Volts

5

604/605

Not used on E3xCxxx models; reports QNAN

VOLTS A-N

Instantaneous Voltage

Ph-A to Neutral

AI4

Volts

5

606/607

Not used on E3xCxxx models; reports QNAN

VOLTS B-N

Instantaneous Voltage

Ph-B to Neutral

AI5

Volts

5

608/609

Not used on E3xCxxx models; reports QNAN

VOLTS C-N

Instantaneous Voltage

Ph-C to Neutral

AI6

Volts

5

610/611

Not used on E3xCxxx models; reports QNAN

VOLTS A-B

Instantaneous Voltage

Phase A to B

AI7

Volts

5

612/613

Not used on E3xCxxx models; reports QNAN

VOLTS B-C

Instantaneous Voltage

Phase B to C

AI8

Volts

5

614/615

Not used on E3xCxxx models; reports QNAN

VOLTS A-C

Instantaneous Voltage

Phase A to C

AI9

Volts

5

616/617

Not used on E3xCxxx models; reports QNAN

kWh Energy: 3ph Total

Real Energy - total of

active phases

AI10

kWh

0

618/619

Not used on E3xCxxx models; reports QNAN

kW: 3ph Total

Inst Real Power- total of

active phases

AI11

kW

1

620/621

Not used on E3xCxxx models; reports QNAN

Power Factor: 3ph Total

Inst Power Factor -

average of phases

AI12

PF

0.01

622/623

Not used on E3xCxxx models; reports QNAN

Amps: 3ph Average

(phases 1,2,3)

Inst Current- average of

active phases

AI13

Amps

5

624/625

kW: Phase 1

Instantaneous Real

Power - Phase 1

AI14

kW

1

626/627

Not used on E3xCxxx models; reports QNAN

kW: Phase 2

Instantaneous Real

Power - Phase 2

AI15

kW

1

628/629

Not used on E3xCxxx models; reports QNAN

kW: Phase 3

Instantaneous Real

Power - Phase 3

AI16

kW

1

630/631

Not used on E3xCxxx models; reports QNAN

Power Factor: Phase 1

Instantaneous Power

Factor - Phase A

AI17

PF

0.01

632/633

Not used on E3xCxxx models; reports QNAN

Power Factor: Phase 2

Instantaneous Power

Factor - Phase B

AI18

PF

0.01

634/635

Not used on E3xCxxx models; reports QNAN

Power Factor: Phase 3

Instantaneous Power

Factor - Phase C

AI19

PF

0.01

636/637

Not used on E3xCxxx models; reports QNAN

Amps: Phase 1

Instantaneous Current -

Phase 1

AI20

Amps

5

638/639

Amps: Phase 2

Instantaneous Current -

Phase 2

AI21

Amps

5

640/641