Enercept H8035 Series Energy Meters (all models)

The H8035 Series has 3 data objects and operates at 9600 baud.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Analog_input objects: (Read-only)
kWh Energy: Total

Accumulated Real Energy

AI1

kWH

0

40259/40260

kW: Total

Total Instantaneous Real Power

AI2

kW

1

40261/40262

Analog_Value objects: (can be written as well as read)
kWh Energy Reset

Write zero to reset

AV1

n/a

32767

40001