Connecting to the RS-232C Port at the Host

64

C200HX/HG/HE(-Z)E: Serial Communications Board port B

Word #

Writing Value

Settings

DM6550

0001

Host link mode, no CTS control
Communication conditions set by the contents of DM

DM6551

0303

Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps

0304

Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps

DM6553

0000

Unit # 00

CPM1: Peripheral port connection through a CPM1-CIF01 RS-232C Adapter

Word #

Writing Value

Settings

DM6650

0001

Host link mode
Communication conditions set by the contents of DM

DM6651

0303

Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps

0304

Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps

DM6653

0000

Unit # 00

Connecting to a CPM2C
The CPM2C PCs do not have the same kind of port connectors found on
CS1-series PCs. The CPM2C’s communication port handles both RS-232C and
peripheral port connections which are divided internally. Therefore, when using
the CPM2C, it is necessary to select RS-232C or peripheral port connections,
according to the kind of cable and port (on the cable) used, as shown in the fol-
lowing table. Refer to the CPM2C Operation Manual for more details.

Port connecting to PT

PC Setup

RS-232C port (D-Sub 9-pin) of CPM2C-CN111

Built-in RS-232C port settings

Peripheral port of CPM2C-CN111

Peripheral port settings

RS-232C port (D-Sub 9-pin) of CS1W-CN118

Built-in RS-232C port settings

Peripheral port of CS1W-CN114

Peripheral port settings

Peripheral port

RS-232C port
(D-Sub 9-pin, female)

CPM2C-CN111

CPM2C

RS-232C port
(D-Sub 9-pin, female)

CS1W-CN118

CPM2C

Peripheral port

CS1W-CN114

CPM2C

Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1, or CQM1H
When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H, the DIP switches on
the front panel must be set as shown below in order to make the settings in the
PC Setup area (data memory) effective.

C200HX/HG/HE(-Z)E

CQM1

CQM1H

RS-232C port communication condition setting

Set DIP SW5 to OFF to make the settings made
in PC Setup effective.