3-5

Section

Using a Memory Unit (-Vj Versions)

41

The functions of the DIP switches on the memory unit are indicated in the table
below.

• SW1

Switch

Function

SW1 1

Automatic transmission (writing from the memory

OFF: Not executed

SW1-1

Automatic transmission (writing from the memory
unit to the PT)

ON : Executed

SW1 2

Automatic transmission (writing from the PT to

OFF: Not executed

SW1-2

Automatic transmission (writing from the PT to
the memory unit)

ON : Executed

SW1 3

Manual transmission (Direction of transmission

OFF: Not executed

SW1-3

Manual transmission (Direction of transmission
and bank used selected at the PT touch panel)

ON : Executed

OFF: Screen data

SW1-4

Data type to transfer

ON : System

program

• SW2

Switch

Function

SW2 1

Disable/enable writing to PT

OFF: Disable

SW2-1

Disable/enable writing to PT

ON : Enable

SW2 2

Disable/enable writing to the memory unit

OFF: Disable

SW2-2

Disable/enable writing to the memory unit

ON : Enable

SW2 3

Area (bank) selection of automatic transmission *

OFF: Bank 0

SW2-3

Area (bank) selection of automatic transmission. *

ON : Bank 1

SW2 4

System/Screen simultaneous transmission

OFF: Disable

SW2-4

System/Screen simultaneous transmission

ON : Enable

* The memory unit stores system program or screen data for one PT in each of

areas (bank 0, bank 1). (The total data storage is for two PTs.) SW2-3 sets which
of these two banks is used for automatic transmission.

Reference:

S The DIP switch function of the memory unit is supplemented to NT31/NT31C

with the V

j suffix.

S In the following cases, a mode setting error occurs.

• More than one of the SW1-1 to SW1-3 switches are set to ON.
• None of the SW1-1 to SW1-3 switches are set to ON.

S In the following case, a protect setting error occurs.

Transmitting to the write destination has been disabled by the setting for
SW2-1 or SW2-2.

S In the following cases, a data transmission error occurs.

• An attempt is made to transmit data other than the system program to PT

system program area.

• An attempt is made to transmit the system program to PT screen data

area.

S For details on mode setting errors and protect setting errors, refer to Errors

When Using a Memory Unit (page 45).

DIP Switch Functions