Connecting to the Support Tool

35

3-2

Connecting to the Support Tool

In order to install the system program in the NT31/NT31C, or to transmit screen
data created with the Support Tool to the NT31/NT31C, the NT31/NT31C must
be connected to a personal computer with an RS-232C cable.

The NT31/NT31C connects the RS-232C cable from a personal computer at se-
rial port A. When the host is connected at serial port B, the connection with the
host can be maintained as it is while the NT31/NT31C is connected to the
RS-232C cable from a personal computer.

However, when a bar code reader is being used, it must be disconnected, so that
the RS-232C cable can be connected, since they both use serial port A.

PRINTER

PORT B

PORT A

Serial port A

(RS-232C, 9-pin)

Communication Conditions
The communication conditions are automatically set when the system installer
and Support Tool are started.

Recommended Connector Cable
Use the cable indicated below.
• CV500-CN228 (length: 2 m), made by OMRON

(D-SUB 9-pin, male

⇔ D-SUB 25-pin, male)

• XW2Z-S001 (conversion cable), made by OMRON

(D-SUB 25-pin, female

⇔ half pitch 14-pin, male)

• XW2Z-S002 (length: 2 m), made by OMRON

(D-SUB 9-pin, male

⇔ D-SUB 9-pin, female)

For details on making a connector cable, refer to Appendix F Making the Cable
for Connecting a PC
(page 269).