2 connecting to the host’s rs-422a/485 port – Omron Programmable Terminals NT31 NT31C User Manual

Page 111

background image

5-2

Section

Connecting to the Host’s RS-422A/485 Port

100

In order to set the terminal resistance, wiring work is required at the cable’s con-
nector: carry out the wiring correctly by referring to APPENDIX E Making the
Cable, page 267.

Abbreviation

FG

-

-

TRM

RDB (+)

SDB (+)

-

-

-

Pin number

Connector

hood

-

9

10

11

12

-

25

Terminal resistor setting

Pin Nos. 9 and 10

Function

Shorted

Terminal resistance is applied.

Short only at the NT31/NT31C connected to the end of an
RS-422A/485 cable.

Open

Terminal resistance is not applied.

Leave the terminals open when connecting an NT31/NT31C
anywhere other than at the end of the RS-422A/485 cable.

Note Before connecting or disconnecting cables between devices, make sure that the

power supply to all of the connected devices (NT31/NT31C, PC, etc.) is OFF.

Reference:

S The internal circuit of the NT31/NT31C is shown below.

16 (RDA)

9 (TRM)

10 (RDB)

+

Terminal resistor (120

Ω)

Making a connection here inserts a terminator between
+ (RDB) and

− (RDA).

S For details on setting the terminal resistance of NT-AL001-E, refer to Settings

at the RS-232C/RS-422A Convertor Unit (NT-AL001-E) (page 88).

5-2

Connecting to the Host’s RS-422A/485 Port

The methods for connecting the RS-422A/485 port of the NT31/NT31C and the
RS-422A/485 port of the host are described here. There are the following meth-
ods.

The following discussion is focused on the connection method to OMRON PCs
(By using the memory link method, a connection can be made to any arbitrary
RS-422 unit). When making a connection to a host other than OMRON PCs, re-
fer to the PC Connection Manual (V042-E1-

j) or Multi Vendor Connection

Manual (V060-E1-

j).

• Method in which the RS-422A ports of the NT31/NT31C and host are con-

nected directly by an RS-422A cable (page 117).

When this method is used, the cable length can be extended up to 500 m.

PT

Host

RS-422A cable

(max. 500 m)

• Method in which the RS-485 ports of the NT31/NT31C and host are connected

by an RS-485 cable (page 121).

When this method is used, the cable length can be extended up to 500 m.