beautypg.com

Omron Programmable Terminals NT31 NT31C User Manual

Page 74

background image

4-1

Section

Connecting to the RS-232C Port at the Host

63

PC Setup Area Settings

When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,
CPM2C, CQM1, or CQM1H CPU, or SRM1, set the following communication
conditions for the PC Setup area.

Item

Setting at Host

Communication mode

Host link mode

Communications speed

Set the same speed as set at the NT31/NT31C

(*1)

Stop bit

2 stop bits

Parity

Even

Data length

ASCII 7 bits

Unit #

00

*1 Set the host link communications speed at 9600 bps or 19200 bps with the

memory switch at the NT31/NT31C. For details, refer to Settings the Host Link
Method
(page160).

Set the PC Setup area settings directly from a Programming Device (e.g. the
CX-Programmer support software).

For details on operations relating to the PC Setup area, refer to the manual for
the PC which is used.

The PC Setup area word numbers and settings to be made depending on the
unit and port to which the connection is made are shown below.

CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection

Word #

Writing Value

Settings

DM6650

0001

Host link mode, no CTS control
Communication conditions set by the contents of DM

DM6651

0303

Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps

0304

Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps

DM6653

0000

Unit # 00

C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than
the CPU11), or SRM1: Built-in RS-232C port connection

Word #

Writing Value

Settings

DM6645

0001

Host link mode, no CTS control
Communication conditions set by the contents of DM

DM6646

0303

Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps

0304

Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps

DM6648

0000

Unit # 00

C200HX/HG/HE(-Z)E: Serial Communications Board port A
CQM1H: Serial Communications Board port 1

Word #

Writing Value

Settings

DM6555

0001

Host link mode, no CTS control
Communication conditions set by the contents of DM

DM6556

0303

Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps

0304

Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps

DM6558

0000

Unit # 00