5-2

Section

Connecting to the Host’s RS-422A/485 Port

106

Connecting to a CVM1/CV Series Host Link Unit

CVM1/CV series rack-mounting type: CV500-LK201

A CVM1/CV series host link unit (CV500-LK201) has two connectors (commu-
nication ports 1 and 2). To use the RS-422A type host link method, set commu-
nication port 2 to RS-422A.

Communication port 2 is a 9-pin connector which allows selection of the
RS-232C or RS-422A method. When this port is used with the RS-422A method,
the I/O port selector switch on the front of the unit must be set to RS-422A (the
lower position).

CPU Bus Unit Settings
When connecting to a CVM1/CV series host link unit, set the following commu-
nication conditions for the CPU bus unit settings.

Item

Setting at Host

Communications speed

Set the same speed as for the NT31/NT31C.

(*1)

Transfer code

ASCII, 7 data bits, 2 stop bits

Parity

Even

1-to-1/1-to-N

1-to-N

(*2)

Instruction level

Level 1, 2, 3

*1 Set the host link communications speed at 9600 bps or 19200 bps with the

Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting
the Host Link Method
(page 158).

*1 The 1-to-N setting enables BCC (Block Check Character). It is not actually

possible to connect more than one NT31/NT31C in a single host link.

Set the CPU bus unit settings directly from a Programming Device (e.g. SYS-
MAC support software).

For details on the CPU bus unit settings, refer to the SYSMAC CVM1/CV-series
Host Link Unit Operation Manua
l (W205-E1-

j).