Omron Programmable Terminals NT31 NT31C User Manual
Page 117
![background image](/manuals/206143/117/background.png)
5-2
Section
Connecting to the Host’s RS-422A/485 Port
106
Connecting to a CVM1/CV Series Host Link Unit
CVM1/CV series rack-mounting type: CV500-LK201
A CVM1/CV series host link unit (CV500-LK201) has two connectors (commu-
nication ports 1 and 2). To use the RS-422A type host link method, set commu-
nication port 2 to RS-422A.
Communication port 2 is a 9-pin connector which allows selection of the
RS-232C or RS-422A method. When this port is used with the RS-422A method,
the I/O port selector switch on the front of the unit must be set to RS-422A (the
lower position).
CPU Bus Unit Settings
When connecting to a CVM1/CV series host link unit, set the following commu-
nication conditions for the CPU bus unit settings.
Item
Setting at Host
Communications speed
Set the same speed as for the NT31/NT31C.
(*1)
Transfer code
ASCII, 7 data bits, 2 stop bits
Parity
Even
1-to-1/1-to-N
1-to-N
(*2)
Instruction level
Level 1, 2, 3
*1 Set the host link communications speed at 9600 bps or 19200 bps with the
Comm. Speed memory switch at the NT31/NT31C. For details, refer to Setting
the Host Link Method (page 158).
*1 The 1-to-N setting enables BCC (Block Check Character). It is not actually
possible to connect more than one NT31/NT31C in a single host link.
Set the CPU bus unit settings directly from a Programming Device (e.g. SYS-
MAC support software).
For details on the CPU bus unit settings, refer to the SYSMAC CVM1/CV-series
Host Link Unit Operation Manual (W205-E1-
j).