5-2

Section

Connecting to the Host’s RS-422A/485 Port

117

When connecting to the host with the memory link method, it is necessary to
create a program for the memory link at the host side.

The following are the communication conditions that can be used with the
memory link method. For the host (a personal computer, an FA computer, etc.),
its setting should be compatible to one of the communication conditions listed in
the following table. Set the same communication conditions at the NT31/NT31C
by the memory switch. (page 165).

Item

Setting at Host

Input/Output board

RS-422A

Communication speed

1200, 2400, 4800, 9600, 19200, 38400 bps.

Data bits length

7 bits, 8 bits

Stop bits length

1 bit, 2 bits

Parity

None, even, odd

Flow control

None, XON/XOFF

5-2-2 Direct Connection between RS-422A Ports at Both Units

The connection method in which the RS-422A ports of an NT31/NT31C and a
host are connected is described here.

NT31/NT31C

Host link/CPU/

Communication unit

SYSMAC

CS1 series PLC,

C series PLC,

CVM1/CV series

PLC, SRM1

9-pin connector or

25-pin connector

Serial port B

(RS-422A, 25-pin type)

25-pin

connector

RS-422A cable with connectors (max. length: 500m)

Connecting an NT31/NT31C and Host (RS-422A)

NT31/NT31C

RS-422A

Host

Wiring When Connecting a C-series Host Link Unit or CPM1 (Host Link)
Applicable units:

C200H-LK202-V1

3G2A5-LK201-EV1