6-11

Section

System Maintenance

218

For Memory Link
Example:
Serial port A while using the memory link

The check is started as soon as the check screen is displayed. Send the com-
mand from the host.
• If communication with the host is normal, the data received from the host is dis-

played in hexadecimal text code at Received Data.

• If nothing is displayed at Received Data when the command is sent from the

host, there is a communication fault: check the communication cables and set-
tings.

For a Bar Code Reader

The check starts when the check screen is displayed. Read data with the bar
code reader in this status.
• If communication with the bar code reader is normal, the read character strings

are displayed in hexadecimal text code at Received Data.

• If nothing is displayed at Received Data when data is read with the bar code

reader, there is a communication fault: check the communication cables and
settings.