Reference

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 80 of 175

ProSoft Technology, Inc.

February 3, 2011

SLC-500 Command Set Functions

Command Function Definition

Supported in Slave

0x0F

0xA1

Protected Typed Logical Read With Two Address

Fields

X

0x0F

0XA2

Protected Typed Logical Read With Three Address

Fields

X

0x0F

0XA9

Protected Typed Logical Write With Two Address

Fields

X

0x0F

0XAA

Protected Typed Logical Write With Three Address

Fields

X

0x0F

0XAB

Protected Typed Logical Write With Mask (Three

Address Fields)

In the client driver, the MVI71-DFNT module is responsible for issuing read or

write commands to servers on the Ethernet/IP network using explicit, connected

messaging. These commands are user configured in the module via the Client

Command List received from the module's configuration file (DFNT.CFG).

Command status is returned to the processor for each individual command in the

command list status block in the command control data area. Ladder logic is

responsible for acquiring this data from the module. The following flow chart and

associated table show the flow of data into and out of the module.

Client Driver