5.6.2 Remote STS Error Codes
Code (Int)
Code (Hex) Description
0
0x0000
Success, no error
4096
0x1000
Illegal command or format
8192
0x2000
Host has a problem and will not communicate
12288
0x3000
Remote node host is missing, disconnected or shut down
16384
0x4000
Host could not complete function due to hardware fault
20480
0x5000
Addressing problem or memory protect rungs
24576
0x6000
Function not allowed due to command protection selection
26872
0x7000
Processor is in Program mode
-32768
0x8000
Compatibility mode file missing or communication zone problem
-28672
0x9000
Remote node cannot buffer command
-24576
0xA000
Wait ACK (1775-KA buffer full)
-20480
0xB000
Remote node problem due to download
-16384
0xC000
Wait ACK (1775-KA buffer full)
-12288
0xD000
Not used
-8192
0xE000
Not used
0xF0nn
Error code in the EXT STS byte (nn contains EXT error code)