Reference

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 102 of 175

ProSoft Technology, Inc.

February 3, 2011

5.5.8 Pass-Through Server Configuration Error Word

The format of the pass-through server configuration error word is as follows:

Bit

Description

Value

0

Invalid enable code

0x0001

1

Invalid busytimeout setting (< 100 milliseconds)

0x0002

2

0x0004

3

0x0008

4

0x0010

5

Invalid baud rate

0x0020

6

Invalid parity

0x0040

7

Invalid data bits

0x0080

8

Invalid stop bits

0x0100

9

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

5.5.9 Pass-Through Server State Parameter

The values for the pass-through server state parameter have the following

definition:

State

Definition

-1

Listen function called to set up server

0

Waiting for connection to be established on server

1

Waiting and processing data received

2

Waiting for pass-through port to be free

3

Pass-through server owns port and processes all data received and written.

100

Closing server on program termination

1000

Initiate a close on the server

1001

Waiting for server to successfully close

The connection state for the pass-through server is not used at this time.