Installing and Configuring the Module

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 30 of 175

ProSoft Technology, Inc.

February 3, 2011

0 to 10000 milliseconds

ACK Timeout

This parameter specifies the number of milliseconds to wait for a DLE-ACK

character sequence after a response is issued.

2.2.4 [DFNT Client 0]

This section is used to define the configuration for the master device simulated

on network port

[DFNT Client 0]

Minimum Command Delay : 30 #Minimum number of msec’s between commands

Response Timeout : 1000 #Response message timeout (0-5000 mSec)

Retry Count : 3 #Response failure retry count

0 to 65535 milliseconds

Minimum Command Delay

This parameter specifies the number of milliseconds to wait between the initial

issuances of a command. This parameter can be used to delay all commands

sent to servers to avoid "flooding" commands on the network. This parameter

does not affect retries of a command as they will be issued when failure is

recognized.

0 to 65535 milliseconds

Response Timeout

This is the time in milliseconds that a Client will wait before re-transmitting a

command if no response is received from the addressed server. The value to use

depends on the type of communication network used, and the expected

response time of the slowest device on the network.

0 to 10

Retry Count

This parameter specifies the number of times a command will be retried if it fails.