MVI71-DFNT ♦ PLC 5

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 153 of 175

February 3, 2011

Select the

C

OMMUNICATION

C

OMMAND

to execute from the following list of

supported commands.

PLC5 Type Read

PLC2 Unprotected Read

PLC5 Typed Read to PLC

PLC Typed Logical Read

The

T

ARGET

D

EVICE

D

ATA

T

ABLE

A

DDRESS

must be set to a valid file element

(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Read

message, set the address to the database index (such as, 1000) to consider with

the command.
The

M

ULTI

H

OP

option must be set to

Y

ES

.

The

M

ULTI

H

OP

tab portion of the dialog

box must be completed as shown in the following window:

Set the IP address value to the module’s Ethernet IP address. You must press

the "Insert" key to add the second line for ControlLogix Backplane and set the

slot number to zero.

5.16.4 SLC 5/05 Processor

The module can be used to receive messages from a SLC 5/05 containing an

Ethernet interface. The module supports both read and write commands. A

discussion of each operation is provided in the following topics.

Write commands transfer data from the SLC processor to the DFNT module. An

example rung used to execute a write command is shown in the following

diagram:

SLC5/05 Write Commands