ProSoft Technology MVI71-DFNT User Manual
Page 153

MVI71-DFNT ♦ PLC 5
Reference
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 153 of 175
February 3, 2011
Select the
C
OMMUNICATION
C
OMMAND
to execute from the following list of
supported commands.
PLC5 Type Read
PLC2 Unprotected Read
PLC5 Typed Read to PLC
PLC Typed Logical Read
The
T
ARGET
D
EVICE
D
ATA
T
ABLE
A
DDRESS
must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Read
message, set the address to the database index (such as, 1000) to consider with
the command.
The
M
ULTI
H
OP
option must be set to
Y
ES
.
The
M
ULTI
H
OP
tab portion of the dialog
box must be completed as shown in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.
5.16.4 SLC 5/05 Processor
The module can be used to receive messages from a SLC 5/05 containing an
Ethernet interface. The module supports both read and write commands. A
discussion of each operation is provided in the following topics.
Write commands transfer data from the SLC processor to the DFNT module. An
example rung used to execute a write command is shown in the following
diagram:
SLC5/05 Write Commands