ProSoft Technology MVI71-DFNT User Manual
Page 79
MVI71-DFNT ♦ PLC 5
Reference
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 79 of 175
February 3, 2011
When using PLC5 or SLC commands, access to the database is through
simulated "N" files. For example, to access database element 3012, use the file
address of N40:12. When using CIP Data Table Read or Write commands, use
the various data[ ] tag arrays described in the following table. For example, use
int_data[3012] to access database register 3012 as an integer value.
Data Type Tag Name
Length of Each Element in
CIP message
Array Range for 4000
Element Database
BOOL
BOOLData[ ]
1
0 to 63999
Bit Array
BITAData[ ]
4
0 to 1999
SINT
SINTData[ ]
1
0 to 7999
INT
INT_Data[ ]
2
0 to 3999
DINT
DINTData[ ]
4
0 to 1999
REAL
REALData[ ]
4
0 to 1999
Before attempting to use the module on a network, verify that the DFNT module
is correctly configured and connected to the network. A network program such as
PING can be utilized to make certain the module can be seen on the network.
Use ProSoft Configuration Builder to verify correct operation, and to transfer
configuration files to and from the module.
The following table shows the supported commands when the module acts as a
slave (server):
Basic Command Set Functions
Command Function Definition
Supported in Slave
0x00
N/A
Protected Write
X
0x01
N/A
Unprotected Read
X
0x02
N/A
Protected Bit Write
X
0x05
N/A
Unprotected Bit Write
X
0x08
N/A
Unprotected Write
X
PLC-5 Command Set Functions
Command Function Definition
Supported in Slave
0x0F
0x00
Word Range Write (Binary Address)
X
0x0F
0x01
Word Range Read (Binary Address)
X
0x0F
Typed Range Read (Binary Address)
X
0x0F
Typed Range Write (Binary Address)
X
0x0F
0x26
Read-Modify-Write (Binary Address)
0x0F
0x00
Word Range Write (ASCII Address)
X
0x0F
0x01
Word Range Read (ASCII Address)
X
0x0F
0x26
Read-Modify-Write (ASCII Address)