ProSoft Technology MVI71-DFNT User Manual
Page 28
Installing and Configuring the Module
MVI71-DFNT ♦ PLC 5
User Manual
EtherNet/IP Client/Server Communication Module
Page 28 of 175
ProSoft Technology, Inc.
February 3, 2011
Yes or No
Enabled
This parameter determines if the server will be utilized by the module. If a value
of "Yes" is entered, the server will be used. Any other value will disable the
server.
0 to 254
Local Station ID
This parameter specifies the local station ID for all DF1 messages sent to this
port. A value of 255 is not permitted as this is the broadcast address. The
application will only accept messages with this node address.
F (Full duplex) or H (Half duplex)
Protocol
The value selected should match that set for the PLC processor.
BCC or CRC
Termination Type
This parameter specifies the error checking for all DF1 messages. Enter BCC or
CRC.
1200 to 38400
Baud Rate - 1200 to 38400
This is the baud rate to be used for the port. Enter the baud rate as a value. Baud
rate entries are 1200, 2400, 4800, 9600, 19200, 28800 or 38400.
None, Odd, Even, Mark, Space
Parity
Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.
5, 6, 7 or 8
Data Bits
This parameter sets the number of data bits for each word used by the protocol.
All devices communicating through this port must use the same number of data
bits.