Installing and Configuring the Module

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 28 of 175

ProSoft Technology, Inc.

February 3, 2011

Yes or No

Enabled

This parameter determines if the server will be utilized by the module. If a value

of "Yes" is entered, the server will be used. Any other value will disable the

server.

0 to 254

Local Station ID

This parameter specifies the local station ID for all DF1 messages sent to this

port. A value of 255 is not permitted as this is the broadcast address. The

application will only accept messages with this node address.

F (Full duplex) or H (Half duplex)

Protocol

The value selected should match that set for the PLC processor.

BCC or CRC

Termination Type

This parameter specifies the error checking for all DF1 messages. Enter BCC or

CRC.

1200 to 38400

Baud Rate - 1200 to 38400

This is the baud rate to be used for the port. Enter the baud rate as a value. Baud

rate entries are 1200, 2400, 4800, 9600, 19200, 28800 or 38400.

None, Odd, Even, Mark, Space

Parity

Parity is a simple error checking algorithm used in serial communication. This

parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.

5, 6, 7 or 8

Data Bits

This parameter sets the number of data bits for each word used by the protocol.

All devices communicating through this port must use the same number of data

bits.