beautypg.com

ProSoft Technology MVI71-DFNT User Manual

Page 75

background image

MVI71-DFNT ♦ PLC 5

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 175

February 3, 2011

This block is sent from the PLC processor to the module when the module is

required to perform a warm-boot (software reset) operation. This block is

commonly sent to the module any time configuration data modifications are made

in the controller tags data area. This causes the module to read the new

configuration information and to restart. The following table describes the format

of the control block.

Warm Boot Block (9998)

Block Request

Offset

Description

Length

0

9998

1

1 to 63

Not used

63

This block is sent from the PLC processor to the module when the module is

required to perform the cold boot (hardware reset) operation. This block is sent to

the module when a hardware problem is detected by the ladder logic that

requires a hardware reset. The following table describes the format of the control

block.

Cold Boot Block (9999)

Block Request

Offset

Description

Length

0

9999

1

1 to 63

Not used

63