ProSoft Technology MVI71-DFNT User Manual
Page 126
Reference
MVI71-DFNT ♦ PLC 5
User Manual
EtherNet/IP Client/Server Communication Module
Page 126 of 175
ProSoft Technology, Inc.
February 3, 2011
5.11.14 Function Code #509 - Protected Typed Logical Write (Two
Address Fields)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address of the
first data point to be associated with the command.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: 0=None, 1=Swap
words, 2=Swap words & bytes and 3=swap bytes in
each word.
6
Node Address
Address of unit to reach on the data highway.
7
Slot Number
Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.
8
Function Code = 509
Logical Write Command
9
File Type
SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….
P1
10
File Number
SLC file number to be associated with the command. P2
11
Element Number
The parameter defines the element in the file where
write operation will start.
P3
12
Not Used
This field is not used by the command. Values entered
in this column will be ignored.
P4
This function writes one or more words of data to a PLC data table.