Reference

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 68 of 175

ProSoft Technology, Inc.

February 3, 2011

5.1.4 Functional Specifications

PLC processor in-chassis EtherNet/IP bridge to optimize data throughput

while communicating with HMI or SCADA and other control platforms without

losing valuable process control bandwidth

Support of up to 4000 PLC registers user data files

User-definable module memory usage

10/100 Base-T Ethernet compatible interface

Functions as a server or a client

Configurable parameters for the client include:

o

A minimum response delay of 0 to 65535 milliseconds

o

A response timeout of 1 to 65535 milliseconds

o

A retry count of 0 to 20

Status data available in ladder logic

Support for PLC processor programming over Ethernet using a TCP/IP service

and a serial port on the module connected to channel 0 of the processor. The

module’s third port emulates Channel 0 of the processor to pass through

messages from the port to the processor

Server Specifications

Supports EtherNet/IP explicit, connected, and unconnected class messaging

Twenty independent server connections permit remote clients to interact with

all data contained in the module

Data can be derived from other clients on the network, through the client on

the module, or from the PLC processor

Client Specifications

Actively issues connected, explicit messages to other nodes on the network

Supports 100 user-defined commands from a single client

Allows command control from ladder logic

Pass-through services

Permits remote programming of the PLC processor on the Ethernet network

via a pass-through

TCP/IP service and a serial communication port (pass-through port) on the

module

The third port on the module can emulate the Channel 0 port on the PLC,

This allows a DF1 master device attached to the emulated (Channel 0) port to

monitor and control data in the PLC