Reference

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 144 of 175

ProSoft Technology, Inc.

February 3, 2011

5.16.2 ControlLogix (CLX) Processor

In order to exchange data between a ControlLogix processor and the module, the

MSG instruction is used. There are two basic methods of data transfer supported

by the module when using the MSG instruction: Encapsulated PCCC messages

and CIP Data Table messages. Either method can be used, and the selection is

left to the application developer.

PLC5 and SLC5/05 processors containing an Ethernet interface use the

encapsulated PCCC message method. The module simulates these devices and

accepts both read and write commands. The following topics describe the

support for the read and write operations.

Encapsulated PCCC Messages

Encapsulated PCCC Write Message
Write commands transfer data from the ControlLogix processor to the module.

The following encapsulated PCCC commands are supported from a ControlLogix

Processor:

PLC2 Unprotected Write

PLC5 Typed Write

PLC5 Word Range Write

PLC Typed Write

An example rung used to execute a write command is shown in the following

diagram:

The

M

ESSAGE

C

ONFIGURATION

dialog box must be completed to define the data

set to be transferred from the processor to the module. An example of the dialog

box follows: