ProSoft Technology MVI71-DFNT User Manual
Page 151
MVI71-DFNT ♦ PLC 5
Reference
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 151 of 175
February 3, 2011
5.16.3 PLC5 Processor
The module can be used to receive messages from a PLC5 containing an
Ethernet interface. The module supports both read and write commands. A
discussion of each operation is provided in the following topics:
Write commands transfer data from the PLC5 processor to the DFNT module. An
example rung used to execute a write command is shown in the following
diagram:
PLC5 Write Commands
In order to complete the configuration of the MSG instruction, select the
S
ETUP
S
CREEN
area of the MSG object. This displays the following dialog box.
Select the
C
OMMUNICATION
C
OMMAND
to execute from the following list of
supported commands.
PLC5 Type Write
PLC2 Unprotected Write
PLC5 Typed Write to PLC
PLC Typed Logical Write
The
T
ARGET
D
EVICE
D
ATA
T
ABLE
A
DDRESS
must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Write
message, set the address to the database index (such as, 1000) to consider with
the command.