beautypg.com

ProSoft Technology MVI71-DFNT User Manual

Page 151

background image

MVI71-DFNT ♦ PLC 5

Reference

EtherNet/IP Client/Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 151 of 175

February 3, 2011

5.16.3 PLC5 Processor

The module can be used to receive messages from a PLC5 containing an

Ethernet interface. The module supports both read and write commands. A

discussion of each operation is provided in the following topics:

Write commands transfer data from the PLC5 processor to the DFNT module. An

example rung used to execute a write command is shown in the following

diagram:

PLC5 Write Commands

In order to complete the configuration of the MSG instruction, select the

S

ETUP

S

CREEN

area of the MSG object. This displays the following dialog box.

Select the

C

OMMUNICATION

C

OMMAND

to execute from the following list of

supported commands.

PLC5 Type Write

PLC2 Unprotected Write

PLC5 Typed Write to PLC

PLC Typed Logical Write

The

T

ARGET

D

EVICE

D

ATA

T

ABLE

A

DDRESS

must be set to a valid file element

(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Write

message, set the address to the database index (such as, 1000) to consider with

the command.