background image

Installing and Configuring the Module

MVI71-DFNT ♦ PLC 5

User Manual

EtherNet/IP Client/Server Communication Module

Page 26 of 175

ProSoft Technology, Inc.

February 3, 2011

Y

ES

or

N

O

Initializing Output Data

This parameter determines if the output data for the module should be initialized

with values from the processor. If the value is set to

N

O

(0), the output data will

be initialized to 0. If the value is set to

Y

ES

(1), the data will be initialized with

data from the processor. Use of this option requires associated ladder logic to

pass the data from the processor to the module.

100 or 1000

DFNT Server File Size

Sets the maximum file size (100 or 1000) for the servers

2.2.2 [DF1 Pass-Through Server Port 1]

This section is used to define the DF1 pass-through server on Port 1 (the second

port)

[DF1 Pass-Through Server Port 1]

Enabled : Yes #Y=Use server, N=Do not use server

Service Port Number : 15000 #TCP service port for this server

Busy Timeout : 500 #Time to wait for not Busy (100-65535

milliseconds)

Baud Rate : 19200 #Baud rate for port 110-19200

Parity : N #N=None,O=Odd,E=Even,M=Mark,S=Space

Data Bits : 8 #5, 6, 7 or 8

Stop Bits : 1 #1 or 2

Yes or No

Enabled

This parameter determines if the server will be utilized by the module. If a value

of "Yes" is entered, the server will be used. Any other value will disable the

server.

1 to 65535

Service Port Number

This parameter sets the TCP/IP service port for this server. Each server can

have its own unique service port or can share the same number with other

servers.

100 to 65535 milliseconds

Busy Timeout

This parameter sets the number of milliseconds the server will wait for the serial

pass-through port to become available. Valid data range for this parameter is 100

to 65535.