ProSoft Technology MVI71-DFNT User Manual
Page 26
![background image](https://www.manualsdir.com/files/866149/content/doc026.png)
Installing and Configuring the Module
MVI71-DFNT ♦ PLC 5
User Manual
EtherNet/IP Client/Server Communication Module
Page 26 of 175
ProSoft Technology, Inc.
February 3, 2011
Y
ES
or
N
O
Initializing Output Data
This parameter determines if the output data for the module should be initialized
with values from the processor. If the value is set to
N
O
(0), the output data will
be initialized to 0. If the value is set to
Y
ES
(1), the data will be initialized with
data from the processor. Use of this option requires associated ladder logic to
pass the data from the processor to the module.
100 or 1000
DFNT Server File Size
Sets the maximum file size (100 or 1000) for the servers
2.2.2 [DF1 Pass-Through Server Port 1]
This section is used to define the DF1 pass-through server on Port 1 (the second
port)
[DF1 Pass-Through Server Port 1]
Enabled : Yes #Y=Use server, N=Do not use server
Service Port Number : 15000 #TCP service port for this server
Busy Timeout : 500 #Time to wait for not Busy (100-65535
milliseconds)
Baud Rate : 19200 #Baud rate for port 110-19200
Parity : N #N=None,O=Odd,E=Even,M=Mark,S=Space
Data Bits : 8 #5, 6, 7 or 8
Stop Bits : 1 #1 or 2
Yes or No
Enabled
This parameter determines if the server will be utilized by the module. If a value
of "Yes" is entered, the server will be used. Any other value will disable the
server.
1 to 65535
Service Port Number
This parameter sets the TCP/IP service port for this server. Each server can
have its own unique service port or can share the same number with other
servers.
100 to 65535 milliseconds
Busy Timeout
This parameter sets the number of milliseconds the server will wait for the serial
pass-through port to become available. Valid data range for this parameter is 100