ProSoft Technology MVI71-DFNT User Manual
Page 49
MVI71-DFNT ♦ PLC 5
Diagnostics and Troubleshooting
EtherNet/IP Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 49 of 175
February 3, 2011
4.1.1 Ethernet LED Indicators
LED
State
Description
Data
OFF
No activity on the Ethernet port.
GREEN Flash
The Ethernet port is actively transmitting or receiving data.
Link
OFF
No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.
GREEN Solid
Physical network connection detected. This LED must be
ON solid for Ethernet communication to be possible.
4.1.2 Clearing a Fault Condition
Typically, if the OK LED on the front of the module turns RED for more than ten
seconds, a hardware problem has been detected in the module or the program
has exited.
To clear the condition, follow these steps:
1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed
correctly.
5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the
PLC controller.
If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.