beautypg.com

0 me-ags-n remote troubleshooting – Magnum Energy AGS Network (ME-AGS-N) User Manual

Page 98

background image

© 2012 Magnum Energy, Inc.

92

12.0 ME-AGS-N Remote Troubleshooting

• If

using

SETUP: 04B Gen Run Time, confi rm you have not set

the total run time (start time to the stop time) longer than the

SETUP: 04F Max Gen Run Time setting.

• If

using

SETUP: 04C Gen Run Amps, confi rm the inverter load(s)

that is used to determine the Stop Gen AC Amps setting is not

required to run longer than the SETUP: 04F Max Gen Run Time

setting.

• If

using

SETUP: 04D Gen Run SOC, confi rm that the METER: 04A

BMK SOC reading is not “Think’n”, but shows an actual percent-

age reading on the display (i.e., 85%), and the Stop Gen SOC

setting can be satisfi ed before the SETUP: 04F Max Gen Run

Time setting is reached.

• If

using

SETUP: 04E Gen Run Temp, the temperature around

the remote temperature sensor has not reached the Gen Run

Temp setting. You need to either lower the Gen Run Temp Start

setting, determine how to cool the area (remote temp sensor

location) to below the Gen Run Temp Start setting before the

04F Max Gen Run Time setting is reached, or increase the Max

Gen Run Time setting.

Lastly, confi rm that your warm-up and/or cooldown time when added

to your autostop condition does not exceed the SETUP: 04F Max Gen

Run Time setting.

Info: Beginning with Revision 5.2 of the ME-AGS-N, the Max Gen Run

Time setting can be defeated. In some cases, it may be appropriate

to set the Max Gen Run Time setting to OFF. However, this feature is

mainly provided as a safety feature to ensure the generator doesn’t

run longer than the time it takes to reach the autostop conditions or

to expend the generator’s fuel capacity, whichever occurs fi rst – take

this into consideration if this setting is defeated.

• Gen

Run

Fault

– The generator successfully started and ran for more

than two minutes, but the generator unexpectedly stopped by itself be-

fore the active AGS autostop condition was fi nished.

Info: The AGS module determines the generator is running by moni-

toring the gen run sense voltage/signal. When this gen run sense

voltage/signal is no longer available, the AGS thinks the gen is off

or has stopped.

Info: Gen run fault detection is not active if the generator is manu-

ally started.

Remedy:
A) If the generator is still running: Confi rm you are getting the cor-

rect gen run sense signal to the AGS module. For assistance, refer to

Section 6.2 “Generator Starting/Running Troubleshooting”.
B) If the generator is not running: Check the generator for fault

codes and adequate fuel. If neither is an issue, check the genera-

tor’s owner’s manual for troubleshooting tips to determine why it

may have shut down on its own.