9.0 Using the ME-ARC Remote

Table 9-2, Software Differences Between ME-ARC Revisions (Cont.)

AGS Menu

(Button: Menu)

AGS Menu

Selections/Adjustments

Inverter

Level

ME-AGS-N

Required

ME-ARC

Required

SETUP: 04 AGS Setup (Cont.)

04B Gen Run

Time

OFF, ON, Start/Stop =

12AM-12PM

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

04C Gen Run

Amps*

OFF, Start/Stop = 5-60

amps AC

≥ Level 4

≥ Rev 5.0

≥ Rev 2.0

Start/Stop Delay = 0-127

sec., 1-127 min.

04D Gen Run

SOC**

OFF, Start = 20-90%

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Stop = 21-100%

04E Gen Run

Temp

Start = OFF, Ext Input,

65-95F

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Gen Run Temp Time =

0.5-6.0 Hours

Gen Run Temp Time =

0.5-25.5 Hours

≥ Level 1

≥ Rev 5.0

≥ Rev 2.4

04F Max Gen

Run Time

0.0-25.5 Hours

≥ Level 1

Rev 5.0 &

5.1

≥ Rev 2.0

OFF-25.5 Hours

≥ Level 1

≥ Rev 5.2

≥ Rev 2.3

04G Quiet

Time

OFF, ON, Start = 12AM-

12PM

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Stop = 12AM-12PM

Quiet Time Topoff = OFF,

30, 60, 90, 120 min.

04H Gen

Exercise

OFF, Days = 1-255

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Run Hour = 12AM-12PM

Run Time = 0.0-25.5 Hrs

04I Gen

Warm-up

Time

0-127 sec., 1-127 min.

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

04J Gen

Cooldown

Time

0-127 sec., 1-127 min.

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

TECH:

01 Tempera-

tures

AGS: Read Only

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

02 Revisions

AGS: Read Only

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Active AGS Fault

Fault LED = off, Fault sta-

tus = view using METER:

03A AGS Status menu

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Fault LED = blinking, Fault

status = alternates with

inverter/charger status

≥ Level 1

≥ Rev 5.0

≥ Rev 2.3

* Only works with MS-PAE or MS-PE inverters.

** The Gen Start/Stop SOC feature requires the ME-BMK (Battery Monitor).