9.0 Using the ME-ARC Remote
© 2012 Magnum Energy, Inc.
54
9.3.2 Monitoring the AGS using the ME-ARC
The ME-ARC remote’s METER and TECH buttons have additional menus that
are helpful for the proper operation and monitoring of your AGS system.
9.3.2.1 ME-ARC Remote’s AGS METER Button
Press the ME-ARC remote’s METER button, rotate the SELECT knob to the 03
AGS Meter menu, and then press the SELECT knob to access the AGS Meter
read-only menus. Rotate the SELECT knob to view the various AGS meters.
METER: 03A AGS Status Menu
This read-only menu displays the AGS’s current status. There are 26 dif-
ferent status messages that can display to identify what state the AGS is
currently in – only one displays at any one time (refer also to Figure 9-2).
• AC
In
• Gen
Cooldown
• Gen
Warm-up
• Manual
Run
• No
Comm
• Off
• Quiet
Time
• Ready
• Start
Amp
• Start
Exercise
• Start
SOC
• Start
Temp
• Start
Test
• Start
Time
• Start
Topoff
• Start
VDC
•
Gen Run Fault
• Fault
Amp
• Fault
Exercise
• Fault
MaxRn
• Fault
SOC
• Fault
Temp
• Fault
Test
• Fault
Time
• Fault
Topoff
• Fault
VDC
Available statuses are (see Tables 11-1 thru 11-3 for information on each):
AUTO: This selection uses the settings from the SETUP button’s 04 AGS Setup
menus to automatically start and stop the generator. Refer to the 04 AGS Setup
menus in Section 9.1 to set the start and stop parameters for the generator.
ON: The ON selection manually starts the generator by sending a “start”
command from the AGS module. Once the generator is started, it must be
manually stopped, either from an external stop switch or by selecting OFF
from the 03 Gen Control menu, which sends a “stop” command from the
AGS module.
Info: When “ON” is selected, the Magnum inverter will not attempt to
accept the generator AC voltage until the warm-up period is satisfi ed.
Info: You can manually start the generator and have it automati-
cally stop by selecting ON from the 03 Gen Control menu, and then
changing the selection to AUTO to automatically stop the genera-
tor. When AUTO is selected after the generator has been manually
started, it displays the AGS status as “Start VDC” and uses the stop
setting in the SETUP button’s 04A Gen Run VDC menu (even if not
active) or the 04F Max Gen Run Time menu, whichever occurs fi rst.
This is useful if you want to make sure the generator starts before
you leave; the Max Gen Run Time setting ensures the generator does
not run longer than required.
Info: This menu is important when determining if the AGS is work-
ing correctly, or for troubleshooting an AGS installation. For any
fault mode displayed in the status menu, refer to Section 12.0 in
this manual.