9.0 Using the ME-ARC Remote

© 2012 Magnum Energy, Inc.

40

AGS Menu

(Button: Menu)

AGS Menu

Selections/Adjustments

Inverter

Level

ME-AGS-N

Required

ME-ARC

Required

CTRL: 03 Gen

Control

OFF, ON, AUTO, Test

≥ Level 1

≥ Rev 5.0

Rev 2.0

OFF, ON, AUTO

≥ Level 1

≥ Rev 5.0

≥ Rev 2.1

METER: 03 AGS Meters

03A AGS Status (Read Only)

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

03B DC Volts - AGS (Read Only)

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

03C Gen Run Time (Read Only)

≥ Level 1

≥ Rev 5.2

≥ Rev 2.0

03D AGS Temp (Read Only)

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

03E Since Gen Run (Read Only)

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

SETUP: 04 AGS Setup

04A Gen Run

VDC

Start = OFF, 9.0-16.0

(12V), 18.0-32.0 (24V),

36.0-64.0 (48V) VDC

≥ Level 1

≥ Rev 5.0

≥ Rev 2.0

Stop = OFF, 9.0-16.0

(12V), 18.0-32.0 (24V),

36.0-64.0 (48V) VDC,

Float

Start/Stop Delay = 0-127

sec., 1-127 min.

Table 9-2, Software Differences Between ME-ARC Revisions

Autostart Condition

Autostop Condition

See SETUP Menu

Page

Starts on low battery

voltage (DC voltage con-

nected to Terminals #3

and #4)

Stops on higher battery

voltage

04A Gen Run VDC

42

Stops at Float charge

after a set time period

(using Absorb Done

Time setting)

04A Gen Run VDC

(Set Stop Gen Volts

= Float)

42

Stops at Float charge

after battery current re-

quirement is low (using

Absorb Done Amps)

04A Gen Run VDC

(Set Stop Gen Volts

= Float)

42

Stops at Float charge

using a battery SOC set-

ting (using Absorb Done

SOC setting)²

04A Gen Run VDC

(Set Stop Gen Volts

= Float)

42

Starts at a set time daily

Stops at a different set

time daily

04B Gen Run Time

44

Starts on high AC amps

to an inverter load¹

Stops on lower AC amps

to an inverter load¹

04C Gen Run Amps

44

Starts when the battery

SOC² is low

Stops when the battery

SOC² is higher

04D Gen Run SOC

45

Starts when tempera-

ture increases

Stops after a set time

period

04E Gen Run Temp

46

Table 9-1, ME-ARC Autostart/Autostop Matrix

Note¹: Only applicable to MS-PAE and MS-PE inverters.

Note²: Autostart/stop conditions using SOC require the ME-BMK (Battery Monitor).