Tech: 01 temperatures, Tech: 02 revisions, Enabling the me-ags-n using the me-rc – Magnum Energy AGS Network (ME-AGS-N) User Manual
Page 42: 0 using the me-rc remote

8.0 Using the ME-RC Remote
© 2012 Magnum Energy, Inc.
36
To manually stop the generator (only if autostarted by AGS):
1. Press the AGS button. The 01 AGS Control menu displays.
2. Press the SELECT knob. The current gen control setting displays with an
arrow to the right.
3. Turn the SELECT knob to the AGS = Off setting.
4. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen and the display returns to the 01 AGS
Control menu. The generator should stop at this time.
If the generator does not stop as expected, refer to Section 12.0.
TECH: 02 Revisions
This read-only menu displays the fi rmware revision level of the AGS module
that is installed and networked.
8.4. Enabling the ME-AGS-N using the ME-RC
Before the AGS can begin operating/monitoring for an autostart condition (us-
ing the active AGS settings in your ME-RC remote control), it must be enabled.
To enable the AGS:
1. Press the AGS button. The 01 AGS Control menu displays.
2. Press the SELECT knob. The current gen control setting displays with an
arrow to the right.
3. Turn the SELECT knob to the AGS = Enable setting (or to Enable w/QT).
4. Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen.
The AGS is now ready to automatically start/stop the generator once an
autostart condition is satisfi ed.
Note: If power is lost to your remote, the AGS control setting will return to the
default Off setting. Once power is restored, you must enable the AGS again.
Note: Despite enabling the AGS, you must check the AGS’s current status
and ensure the status displays as “Ready”.
Autostop Conditions
•
03 Run Time Hour (page 30)
•
07 Quiet Time (pages 32-33)
Autostart Conditions
•
04 Start Temp F (pages 30-31)
•
05 Start Volts (page 32)
•
07 Quiet Time (pages 32-33)
8.5 Starting and Stopping the Generator using the
ME-RC
The generator can be manually stopped, as well as autostarted/autostopped
using the available settings from your ME-RC (see Section 8.1).
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the follow-
ing autostart/autostop conditions must be pre-set (see Section 9.1):
Press the TECH button, and then rotate and press the SELECT knob to access
the following menus:
TECH: 01 Temperatures
This read-only menu displays the ambient temperature reading of the AGS’s
temperature sensor (if installed). If the temperature sensor is not installed,
the display will either show a very high temperature value (122°C/252°F),
or “TS open” displays – depending on your remote revision.