3.0 ME-AGS-N Module Setup

© 2012 Magnum Energy, Inc.

20

ON

4
3
2
1

RY1

(N.O.)

RY2

(N.O.)

T1

T2

T3

GEN RUN PD.

T3

RY1

(N.O.)

T1

T2

GEN RUN PD.

RY2

(N.O.)

RY3

(N.O.)

T1

T2

GEN RUN PD.

Portable

Mode

T1

=

2 sec.

T1

=

4 sec.

T2

=

10 sec.

2-Wire

Momentary

Mode

T1

=

2 sec.

T2

=

10 sec.

QD Mode

(default)

T1

=

20 sec.

T2

=

4 sec.

T3

=

10 sec.

3-Wire

Mode

T1

=

5 sec.

T2

=

2 sec.

T3

=

10 sec.

Gen

Type

Relay Timing/Operation (RY1/RY2/RY3)

Time

Period

2-Wire

Maintain

Mode

Generator: Quiet Diesel Series (Onan). HDZAA model is not

compatible with the AGS-N module – damage may occur.

Generators: Marquis, Emerald, and Microquiet (Onan); Quiet

Pack Series (Generac).

Generator: EM Series with remote control (Honda).

Generators: RMY Series (Kohler); DynaGen controllers.

Generator: PT-ECU-63 controller with 2-wires (Powertech).

ON

4
3
2
1

ON

4
3
2
1

ON

4
3
2
1

T2

=

10 sec.

RY3

(N.O.)

RY3

(N.O.)

ON

4
3
2
1

RY1

(N.O.)

RY2

(N.O.)

T1

GEN RUN PD.

T3

T2

T3

RY3

(N.O.)

RY1

(N.O.)

RY2

(N.O.)

T2

T1

T1

GEN RUN PD.

RY1

(N.O.)

RY3

(N.O.)

RY2

(N.O.)

T3

=

5 sec.

T3

RY2

(N.O.)

RY3

(N.O.)

T1

T2

GEN RUN PD.

T1

=

4 sec.

T2

=

10 sec.

2-Wire

Standby

Mode*

Generators: Two-wire start (does not require gen run

voltage signal to Terminal #2).

ON

4
3
2
1

T1

=

10 sec.

T2

=

14 sec.

5-Wire

Mode

Generators: BTDA / BEG (Westerbeke), 205-DS (Martin

Diesel), NL-673 (Northern Lights).

RY1

(N.O.)

RY2

(N.O.)

RY3

(N.O.)

T3

=

4 sec.

T4

=

25 sec.

T1

T2

T3

T1

T4

T1

GEN RUN PD.

RY1

(N.O.)

ON

4
3
2
1

* ME-AGS-N Revision 5.2 or higher required

Table 3-1, Gen Type Settings